2 Overview
UPS IST7 Series (60K-200K)
User Manual
18
NO.
Name
Illustration
ALARM
(yellow)
On: system control card have alarm signal.
FAULT
(red)
On: system control card fault.
○
,8 EPO2 input dry contact
Normal close input port of external EPO. The signal is valid
when NC terminal and COM terminal disconnect. The signal is
preset and cannot settable.
○
,9 MODBUS port and
RS232 port
Communication protocol support MODBUS RTU, switch it by
touch screen. MODBUS/RS232 port adopts RJ45 plug to
connect, the Pin definition as shown in Figure2-14, Figure2-15.
○
,10
MDU port
Touch screen communication port.
RS485 port
1--8
RJ45
plug
RJ45
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Pin definition
:
Pin 1
:
White orange-RS485:A
Pin 2
:
Orange-RS485:B
Pin 3
:
White green-Reserved
Pin 4
:
Blue-RS485:B
Pin 5
:
White blue-RS485:A
Pin 6
:
Green-Reserved
Pin 7
:
White brown-Reserved
Pin 8
:
Brown-GND
Figure2-11
Pin definition of RS485
UPS1
Bypass unit
UPS2
Bypass unit
Figure2-12
RS485 port wiring(Two UPSs)