3 Installation
IST6
Series (200K-600K) Modular UPS
User Manual
52
All rights reserved ©
Allis Electric
Co., Ltd.
If the wiring is from upside, it needs to make the cable go through the top styrofoam, and then connect
the cables.
If the wiring is form downside, it needs to knock down the bottom wiring hole, and then connect the
cables.
After connecting, connect the cables onto the front isolation beam of the cabinet shipshape.
It is suggested to equip DC breaker for battery DC input, specific wire connection is as shown in
Figure3-34
Battery wire connection diagram
When wiring, ensure that the input wires, output wires and input terminal, output terminal contact
firmly and must not contact bad or wrong.
Step 4
After wiring, fasten the cables to corresponding epoxy plate by cable tie (as shown in Figure3-35,
Figure3-36), and install the wiring cover plate again, and then install the handle of switch. The wiring
is finished.