IST6
Series (200K-600K) Modular UPS
User Manual
3 Installation
All rights reserved ©
Allis Electric
Co., Ltd.
33
3.2.3 Installation Space
Maintain a clearance of at least 800mm from the front panel or rear panel of the UPS to the wall or
adjacent device, and maintain a clearance of at least 500mm from the top of the UPS to ceiling,
which is to ensure good ventilation, as shown in Figure3-2.
Figure3-2
Installation space (unit: mm)
The installation space requirement for the UPS is the same, in above figure, we take
IST6400
as an
example to illustrate.
Avoid any object block the ventilation hole on the front panel and rear panel, which is to keep
good ventilation for the UPS, or, it may rise the inner temperature, even influence the UPS
service time.
3.2.4 Input and Output Wire Selection
For the wire sectional area selection of AC input and output wires, please refer to Table3-1 for
corresponding recommended values, and choose upwards.