SSBP-3000C
Page 25
5.3.1 E
NVIRONMENTAL AND
A
DEQUATE
V
ENTILATION
C
ONSIDERATIONS
The SSPB contains a forced air cooling system, which prevents the internal components from
overheating and to optimise performance stability. The cooling system consists of three fans to
effectively distribute and remove the air from within the unit.
Prior to installing the SSPB, verify that:
1. Environmental conditions listed in
TABLE 7
will be met.
2. A minimum clearance of 30-cm (12 inches) is necessary in front of the air intake openings on
the rear panel.
3. The grill of the fan intake and the exhaust openings of each AWTX are free of any obstructing
debris.
TABLE 7:
ENVIRONMENTAL CONDITIONS
Temperature:
Non-operating (continuous exposure)
Operating (ambient)
-40 °C to + 55 °C
0 °C to + 50 °C
Relative Humidity:
Up to 90% relative humidity, non-condensing
Altitude:
10,000 feet AMSL, de-rated 2°C/1,000 feet from AMSL
5.3.2 M
ECHANICAL
I
NSTALLATION
5.3.2.1 Mounting Considerations
For a proper installation, the SSPB requires a standard 19-inch equipment rack and must be
secured by the front panel. Prior to installing the SSPB ensure that at least two individuals lift and
position the unit on to the equipment rack.
5.3.2.2 Installation Procedure
Install the SSPB into the 19-inch rack as follows:
CAUTION:
Obstructing objects or debris may reduce the efficiency of the cooling system
and significantly impact uponon the longevity of the SSPB.
Summary of Contents for SSPB-3000C
Page 10: ...SSBP 3000C Page 9 Figure 1 Product Outline...
Page 17: ...SSBP 3000C Page 16 Figure 3 Front Panel Assembly...
Page 25: ...SSBP 3000C Page 24 Figure 5 Connectors Location on Front and Back Panels...
Page 36: ...SSBP 3000C Page 35 Figure 7 RS 232 Communication via HyperTerminal...
Page 38: ...SSBP 3000C Page 37 Figure 8 Help function in HyperTerminal...
Page 50: ...SSBP 3000C Page 49 Figure 9 Redundant System rear view...
Page 51: ...SSBP 3000C Page 50 Figure 10 Redundant System lateral right view...
Page 52: ...SSBP 3000C Page 51 Figure 11 Redundant System lateral left view...
Page 53: ...SSBP 3000C Page 52 Figure 12 Redundant System top view...
Page 54: ...SSBP 3000C Page 53 Figure 13 RS 232 Communication via HyperTerminal for Redundant System...