CONVERTER-TRANSMITER

.- Series CCT

CCT- 20 .- for PT100 Signals
CCT- 90 .- Potentiometer Signals
CCT- 95 .- Resistance Signals

P.I. Santiga Altimira 14 (Talleres 14, Nave 2)

E 08210-BARBERÀ DEL VALLÈS (SPAIN)

Tel:  (+34) 93.729.6004 Fax : (+34) 93.729 .6003

[email protected]        www.fema.es

2.- ADJUST AND CALIBRATION PROCEDURE

1.- Open the housing to access the instrument internal circuits
2.- Select apropriate jumpers on boards ME, MP and MS
3.- Connect signal generator to signal input terminals

Connect multimeter to signal output terminals

4.- Power up the instrument as indicated on the label
5.- Generate the signal level low

Operate potentiometer P1 on ME until indication shows desired signal output low level

6.- Generate the signal level high

Operate potentiometer  P2 on ME until indication shows desired signal output low level

7.- Repeat steps 6 to 9 in order to correct deviations and check adjust

Weight

270 gr.

Wire Crossection

4 mm

2

 maximum

Housing and Cover

IP-40

Terminals

IP-20

Housing and Cover

Polycarbonate, Light Grey, RAL  7032, UL 94 V-1

Terminals

Polycarbonate, Dark Grey, UL 94 V-2

Mounting

Standard DIN rail (DIN 46277, DIN EN 50022)
(35 x 7,5mm) (1,38 x 0,3") .

1.- COMMON TECHNICAL SPECIFICATIONS

Output 0/20mA ó 4/20mA R

L

< 600 Ohms max. 22 mA ±3%

Output 0/10 Vdc

R

L

> 1000 Ohms max. 11 V ±3%

Response Time

 250 mSec

Galvanic Isolation

2  KV

eff. 

 50 Hz/1 min (between all circuits)

Isolation Test

4  KV

eff.

 50 Hz/1min

Accuracy

Class

 <

0,2 for CCT-20, CCT-90 and CCT-95

Ripple

 0,5 %

Pass Band

1,5 Hz (-3 dB)

Storage Temperature

-30 to +80 °C (-22 to +176 ºF)

Working Temperature

-10 to +60 °C (+14 to +140 ºF)

Temperature Coef.

 0,015 %/ °C

Power Supply

See label on instrument

Consumption

<1,5 VA

MECHANICAL DIMENSIONS in mm (inches)

45

(1,771")

OUTPUTS / SALIDAS
        mA          Vdc

INPUT / ENTRADA

SU

PPL

Y /

 A

L

IM

EN

T

A

C

IO

N

3    4    5    6

9   10   11   12

7

1

+

Lo

H i 

+

-

-

75

(2,952")

110

(4,33")

36

(1,417")

Summary of Contents for ASGARD CCT Series

Page 1: ...signal output low level 7 Repeat steps 6 to 9 in order to correct deviations and check adjust Weight 270gr Wire Crossection 4 mm2 maximum HousingandCover IP 40 Terminals IP 20 HousingandCover Polycarbonate Light Grey RAL 7032 UL 94 V 1 Terminals Polycarbonate Dark Grey UL 94 V 2 Mounting Standard DIN rail DIN 46277 DIN EN 50022 35 x 7 5mm 1 38 x 0 3 1 COMMON TECHNICAL SPECIFICATIONS Output 0 20mA ...

Page 2: ...SELECTION AND CONNECTIONS Instrument CCT allows outputs in voltage and current Only one of this outputs is active at the same time Is is possible to reconfigure the instrument to any of the indicated output signals below plus the 4 20 mA and 0 10 Vdc signals allowed by default Resistances in Ohms OUTPUT R18 R24 R25 0 5mA 100 0 10mA 49 9 1 5mA 100K 124 0 20mA 24 9 NOTE resistance NOT installed Resi...

Page 3: ...ak Detection Output signa goes lower than the minimum output signal 4mA for example Minimum Input Span Minimum range at input in order to have a maximum output range in 0 10 Vdc or 4 20 mA OUTPUTS SALIDAS mA Vdc INPUT ENTRADA SUPPLY ALIMENTACION 3 4 5 6 9 10 11 12 7 1 Lo Hi PT 100 2 wire OUTPUTS SALIDAS mA Vdc INPUT ENTRADA SUPPLY ALIMENTACION 3 4 5 6 9 10 11 12 7 1 Lo Hi PT 100 3 wire In 2 wire t...

Page 4: ...a and introduce the electrical noise to the unit therefore Do not install the signal input wires in the same conduit with power lines heaters solenoids SCR controls etc and always far from these elements When shielded wires are used leave unconnected the shield on the transmitter side and connect the other end of the shield to the ground terminal of the machine SAFETY CONSIDERATIONS PRESCRIPTIONS ...

Reviews: