6.1
WATER SYSTEM
A.
MOTOR/PUMP ASSEMBLY:
the
motor/pump assembly circulates
chilled fluid to the process loop.
The pump assembly is built of total
stainless steel to maintain water
quality (figure 6.1A).
B.
FLOW SWITCH
: the flow switch is
a paddle-type switch mounted in
the from process water line. The
primary function of the flow switch
is to monitor water flow. If the flow
drops 33%, the switch will stop the
refrigerant circuit. This protects the
evaporator from freezing due to
low flow (figure 6.1B).
C.
FREEZESTAT:
the freezestat aids in
protecting the evaporator from
potential freezing. The freezestat is
factory adjusted to 40°F. The
freezestat must be field adjusted for
operating with setpoints below
48°F (figure 6.1C).
6.2
REFRIGERATION SYSTEM
A.
COMPRESSOR:
hermetic or semi-
hermetic compressors take low
pressure/low temperature
refrigerant gas and compress the
gas into high pressure/high
temperature gas (figure 6.2A).
B.
AIR COOLED CONDENSER:
the air
cooled condenser removes BTU’s
from the compressed refrigerant
gas. The action causes the gas to
“condense” into a liquid state still
under high pressure. Air flow across
the condenser is achieved via a
motor driven fan assembly or
centrifugal blower (figure 6.2B).
C.
FILTER-DRIER:
the filter-drier
removes contaminants and
moisture from the liquid refrigerant
(figure 6.2C).
Flow switch
Figure 6.1B
Mechanical freezestat
Figure 6.1C
Hermetic compressor
Semi-hermetic compressor
Figure 6.2A
Pump Motor Assembly
Figure 6.1A
Summary of Contents for Maximum
Page 2: ......
Page 6: ...Page 6 THIS PAGE INTENTIONALLY BLANK ...
Page 44: ...Page 44 THIS PAGE INTENTIONALLY BLANK ...
Page 58: ...Page 58 THIS PAGE INTENTIONALLY BLANK ...
Page 79: ...END 2003 ADVANTAGE ENGINEERING INC RE 1 2 03 ...
Page 80: ......