MK Series Portable Chiller : Air-Cooled : HE INSTRUMENT
Page: 55
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Email: [email protected]
4.
The cleaning fluid source should have at least 20 psi
available. If acid cleaning, follow the instructions supplied
with the acid solution carefully.
5.
When the procedure is complete, reinstall all water lines to
original factory orientation. Restart the unit and check for
proper operation.
6.
Note:
this procedure is not normal maintenance.
Maintaining proper water quality and filtration will
minimize the need to back flush the evaporator.
5.8
DIP SWITCH ADJUSTMENT
The 5 position DIP switch is located on
the lower right side of the CPU
board
(figure 5.8A).
B.
The switches are used to set
options for machine operation.
C.
The switches should only be
changed when the instrument is
turned OFF.
Typical DIP switch location
Figure 5.8A
CYLINDER CNT - 1 STAGE UNLOADING
CYLINER CNT - 2 STAGE UNLOADING
EXT_CONFIG - DO NOT SHOW EXTENDED CONFIGURATION
EXT_CONFIG - SHOW EXTENDED DISPLAY
SETPOINT RANGE - 48
°
- 70
°
F
SETPOINT RANGE - 90
°
- 10
°
F
CODE_PAGE - PAGE 1, 10000-1FFFF
CODE_PAGE - PAGE0, 0000-0FFFF
CHILLER_TYPE - NO UNLOADING (STD)
CHILLER_TYPE - UNLOADING ENABLED (CYL)
FACTORY SET
OPTIONS
1
2
3
4
5