19
SYSTEM SETTINGS
Fan Settings
ID
Description
Default
Min
Max
P89
Start temperature for Fan#1
60°
1°
99°
P90
Start temperature for Fan#2
66°
1°
99°
P95
Fan #1 DIF1 start temperature
60°
1°
99°
P96
Fan#2 DIF1 start temperature
75°
1°
99°
P101
Fan #1’s DIF2 start temperature
70°
1°
99°
P102
Fan #2’s DIF2 start temperature
71°
1°
99°
P107
Fan temperature gap. Difference between on and off
0.5
P111
Fan #1 Max humidty. If humidity sensor is installed, when
fan #1 will start to dry out the building
99%RH
P112
Fan humidty hysteresis – set to 101% to disable humidity
function
5%
101%
P113
Fan humidity temperature limit
32°
The temperature parameters control the starting temperature.
The fans are used for cooling. They will turn on above the temperature setpoint.
If humidity is connected , fan # 1 can be set to clear out the high humidity.