When the panel module is mounted in 

large 

floor standing rack enclosures, fit the 

MXM-

MXM-534 loop card support plate as 

shown 

opposite. 

Remove the three screws fixing the 

display 

card and replace with the supplied pillars. 

Mount the plate onto the pillars and fix in 

place 

using the supplied screws. 

 

 

 

 

 

2.3.1.1  Wiring 

Cable entry holes are provided for installation wiring 

– two on the right hand side for AC Supply and Battery 

Supply 

– one on the left for internal wiring. Also on the left (top) is a U channel cut-out for routing field wiring to 

the side frame of the enclosure. 

Cable tie anchor points are provided at strategic locations to tie down the wiring. 

Refer to the wiring section of the product manual 680-165 for full information. The AC Supply and Battery 
Supply connections are re-iterated below for reference. 

2.3.1.1.1  AC Supply 

Route the high voltage mains AC wiring into the 
enclosure at the upper right corner only. Keep the 
AC wiring away from the circuit boards and all 
other wiring.  

The mains input connector is shown in the 
diagram below. Note the positions of the earth, 
neutral and live terminal connections. These are 
clearly marked on the label next to the connector. 
The connector block contains an integral fuse 
holder. 

 

F U S E  

B ro w n  

G reen  

L IV E  

E A R T H  

N E U T R A L  

P a n el W irin g  

B lu e  

3 .1 5 A  

 

AC Mains terminations

 

The fuse is rated as follows: 

T 3.15A H 250V 

Replace with correct rating and specification only. 

 

M u s t b e  

e a rth e d  

 

The panels must be connected to 
the supply earth through the power 
cable. 

Secure the mains input wiring by tie wrap as close 
to the terminal block as possible. 

Connect the Control Panel to the mains supply via 
a readily accessible disconnect-device (Isolation 
Switch) and suitable earth fault protection 
incorporated in the building installation wiring. The 
Mains cable should be 0.75mm

2

 cable rated at 

250V and fused via a 5A anti-surge fuse. 

NOTE: If two or more power supplies are installed 
then an MXP-514 AC Filter card kit must be 
installed in the back box. Refer to Section 2.3.5 for 
more details. 

 

 

 

 

 

M3 Pillars 

MXM-534 Plate 

Order separately 

 

Summary of Contents for Mx-5101xR

Page 1: ...www advancedco com 5000 Series Rack Panels The operation and functions described in this manual are available from Software Version Mx5000 050 04 onwards...

Page 2: ...Door with LED Aperture Mxm 513 D3 Enclosure Utility Module 6U Door with Aperture Mxm 513 FP Enclosure Utility Module 6U Fascia Plate Blank Mxm 513 MF Enclosure Utility Module 6U Switch LED Mounting F...

Page 3: ...ECHANICAL SPECIFICATIONS 8 2 2 1 Enclosure 16U 8 2 2 2 Enclosure Other Sizes 9 2 2 3 Enclosure Commercial 9 2 2 4 Battery Gas Venting 9 2 2 5 Battery Shelf Chassis Plate DIN Rail 9 2 2 5 1 MXM 510 BS...

Page 4: ...put to Fault Routing Equipment Investigation Delays to Outputs Dependency on more than one alarm signal Fault Signals from Points Disablement of Points Alarm Counter Test Condition Standardised Input...

Page 5: ...ddition the module assemblies can be mounted into commercial rack mount enclosures This manual covers the installation of the rack mount 5000R 5000VR Series Fire Alarm Control Panel assemblies and enc...

Page 6: ...code of practice or national standard regulations for fire systems installation for example BS5839 1 2002 appropriate to the country and location of the installation 1 5 2 Wiring Regulations The panel...

Page 7: ...l model refer the separate sections in this manual Visual indicators can be seen through the glass panel The outer door is not locked to provide access to Level 1 and Level 2 controls An optional key...

Page 8: ...re and can be fitted behind Zone LED modules or blanking plates Mount the enclosure on the wall using fixing hardware suitable for the size and weight of the complete enclosure 2 The fixing holes are...

Page 9: ...le for the IP rating required 2 2 5 Battery Shelf Chassis Plate DIN Rail 2 2 5 1 MXM 510 BS Up to two battery shelves can be fitted for mounting of 7Ah or 18Ah batteries The shelves rest on the side w...

Page 10: ...her two peripheral bus modules Screw these M3 pillars into the captive nuts on the chassis plate and then mount and affix the modules using the M3 screws supplied with the module The PSE module fits d...

Page 11: ...ox is 125 mm The panel module weight is 6 kg The door is securely locked using the standard Advanced Electronics Ltd panel key The internal arrangement of the panel module is shown in the following di...

Page 12: ...Keep the AC wiring away from the circuit boards and all other wiring The mains input connector is shown in the diagram below Note the positions of the earth neutral and live terminal connections These...

Page 13: ...e battery leads Use the supplied tie wraps to tie the sensor cable to the battery leads so that the encapsulated sensor is located close to the batteries The sensor cable is 500mm in length NOTE If th...

Page 14: ...unting frame using 4x M4 Nuts and washers Connect the ribbon cable to the display card Route the cable through the lower hole in the left hand side of the panel module enclosure and connect to the inp...

Page 15: ...be fitted 2 3 3 1 Chassis The utility chassis plate can accept the following module types 1x PSE Module Mxs 049 Mxs 050 or Mxs 051 and 1x Mxp 510 BMS Interface4 or 1x Mxp 554 ipGateway or 2x standard...

Page 16: ...the Mxs 049 to the upper four holes and fit the Mxs 050 and Mxs 051 to the outer four holes Fit the terminal block to the enclosure using the two supplied M3 Screws and affix the integral earth lead t...

Page 17: ...r hole in the left hand side of the panel module enclosure Route the cable through the lower hole in the left hand side of the utility module enclosure and connect to the input connector top of the fi...

Page 18: ...e can be drilled and screen printing for the required graphic indicator diagram Mimic area 350 W x 180 H Up to two Mxp 539 Input Output Cards are required to be mounted to the chassis LED and Switch o...

Page 19: ...blank plate in the door can be removed so that it can be drilled and screen printed as required for fitting of switches and LED indicators 2 3 4 1 Chassis 6U The 6U Chassis can be fitted refer to pre...

Page 20: ...051 and Up to 4x Mxp 539 Mimic Interface Modules Up to 192 LED and up to 64 Switches 5 Mxp 020 and Mxp 045 modules can also be fitted in this one location An additional Mxs 027 can be also be fitted...

Page 21: ...es and fit the Mxs 050 and Mxs 051 to the outer four holes Fit the terminal block to the enclosure using the two supplied M3 Screws and affix the integral earth lead to the stud using the supplied M4...

Page 22: ...he enclosure Ensure the leads are tie wrapped securely to the module enclosure next to the terminal block Item Specification Details AC Supply Voltage 200 240V 47 63Hz AC 6 AC Supply Current Maximum 4...

Page 23: ...www advancedco com USER NOTES...

Page 24: ...nced Electronics Ltd Moorland Way Cramlington Northumberland NE23 1WE UK Tel 44 0 1670 707 111 Fax 44 0 1670 707 222 Email sales advancedco com Web www advancedco com Doc Number 680 195 Revision 01A F...

Reviews: