5-2 Data Format
6.
Send “
4mA Calibration
$(Addr)0” command to the analog
output module to complete the 4 mA calibration.
7.
Send the “
Analog Data Output
#(Addr)(OutData
)
” command
with output value is
20 mA
. For example if the address is 0x03
then the command is
#0320.000
8.
Use “
Trim calibration
$(Addr)3(Counts)” command to adjust
until the output value to
5 V (20 mA)
.
9.
Send “
20mA Calibration
$(Addr)1” command to the analog
output module to complete the 20 mA calibration.
-IOUT
Calibration wiring of NuDAM-6021
+IOUT
250 Ohms
5 1/2 Digital Meter
+
-