3-8 Initialization & Installation
Figure 3. -1 Data format of Analog Output Setting
*
6024 only supports immediate change and engineering units.
7
6
5
4
3
Reserved
Must to be 0
Analog Output Data Unit
00 : Engineering units
01 : % of Full Scale Range
10 : Hexadecimal
Slew Rate
BitCode
Voltage
Current
0000 immediate change
0001 0.0625
V/sec
0.125
mA/sec
0010 0.125
V/sec
0.250
mA/sec
0011 0.250
V/sec
0.500
mA/sec
0100 0.500
V/sec
1.000
mA/sec
0101 1.000
V/sec
2.000
mA/sec
0110 2.000
V/sec
4.000
mA/sec
0111 4.000
V/sec
8.000
mA/sec
1000 8.000
V/sec
16.00
mA/sec
1001 16.00
V/sec
32.00
mA/sec
1010 32.00
V/sec
64.00
mA/sec
1011 64.00
V/sec
128.0
mA/sec
2
1
0
Checksum
0 : disable
1 : enable
Summary of Contents for ND-6021
Page 1: ...ND 6021 ND 6024 Analog Input Modules User s Guide...
Page 14: ......
Page 20: ......
Page 54: ......