MAInTEnAnCE
34
ADICOS GSME
405-2010-003 EN52
Create a backup file
1
Open ADICOS central software
2
Call up “Service functions”
3
Select “Test”
4
Save table
Z
The backup file with all relevant unit data is now located under:
C:\GSME\Melder_Liste_komplett.csv
8.5.2
Prepare new unit for use
If the ADICOS central software is used permanently for monitoring measurement data, it is
necessary to prepare the new device for use at a specific position. A specific position is iden
-
tified by a line number, for example.
The prerequisite for a 1-to-1 exchange of the new unit and the old unit is an
identical MBus address.
►
Adopt the MBus address of the old unit for the new unit before commissioning it on the
MBus.
►
If the alarm thresholds before and after the detector replacement are to be identical,
adopt the alarm thresholds of the old unit for the new unit.
Die MBus-Adresse sowie die Alarmschwellen des Austauschgerätes sind in der
Sicherungsdatei hinterlegt (siehe 8.5.1 Bestandsdaten sichern).
8.5.3
Replace detector
If the ADICOS central software is used permanently for monitoring measurement data, it is
necessary to store the serial number of the new device correctly.
►
For this purpose, adopt the MBus address of the old unit for the new unit on the MBus
before commissioning (see 8.5.2 Prepare new unit for use).
If coupling modules for a fire alarm bus are transferred from old to new units,
make sure that the electronics of the units are protected from external damage
when opening the new units.
When closing the unit, tighten all screw connections with a torque of 1.5 N to
ensure dust-tightness.