S
ETTING
S
CENES
This command is used to activate a specific scene into a DALI device, group or broadcast..
REQUEST
S_SCE_
sc
_
id
(ASCII format)
Where:
‘sc’ = scene to activate (0 ÷ 15);
‘id’ = ID of the DALI node (0 ÷ 63) or group (64 ÷ 79) or broadcast (80).
Note:
Just ‘sc’ and ‘id’ are variable, the rest of the ASCII string is fixed.
Note:
In order to address the Serial command to a specific converter in the serial line, it is necessary to add at the start of the commands
the chars “nnn.” where ‘nnn’ is the ID Board set in section “Set Communication” of SW67831. The response will contain the additional chars