Industrial
Electronic Devices
ADFweb.com Srl – IT31010 – Mareno – Treviso INFO:
www.adfweb.com
Phone +39.0438.30.91.31
User Manual
DALI / Serial - Converter
Document code: MN67831_ENG Revision 1.100 Pagina 47 di 56
Setting new Fade Time value
This command is used to program the new Fade Time value in the DALI devices.
REQUEST
S_TIM_
id
_
val
(ASCII format)
Where:
‘id’ = ID of the DALI node (0 ÷ 63) or group (64 ÷ 79) or broadcast (80).
‘val’ = value of new Fade Time value to set (0 ÷ FF, Hex representation)
Note:
Just ‘id’ and ‘val’ are variables, the rest of the ASCII string is fixed.
Note:
In order to address the Serial command to a specific converter in the serial line, it is necessary to add at the start of the commands
the chars “nnn.” where ‘nnn’ is the ID Board set in section “Set Communication” of SW67831. The response will contain the additional chars
too.