ADEY DEK1001 MODBUS PROTOCOL – VARIABLE LIST
DEFAULT SETTINGS
BAUD RATE
9600
WORD LENGTH
8
PARITY
NO
STOP BITS
1
X Variable
Address
Denomination
Type
X Variable
Format
Data Conversion
Units
Equivalent
Range
Range of
X Variable
Notes
40001
Cartridge Present
read/write
word 16 bits
4 = No 5 = Yes
6 = Fast Fast
4->6
4->6
40002
Magnet Only Service
warning
read/write
word 16 bits
11=Daily
12=Weekly
13=Monthly
11->13
11->13
40003
Magnet Only Service
warning Duration
read/write
word 16 bits
Value = X
1->12
1->12
40004
Parameter Pressure
Difference Warning
read/write
word 16 bits
Value = X/10
Bar
0,1-0,6
1-6
40005
Parameter Pressure
Difference
read/write
word 16 bits
Value = X/10
Bar
0,1-6,0
1-60
40006
Parameter Sensor
Minimum Pressure
read/write
word 16 bits
Value = X/10
Bar
0 - Par.7
0- Par.7
See
note 1
40007
Parameter Maximum
Pressure
read/write
word 16 bits
Value = X/10
Bar
Par.6-6,0
Par.6-60
See
note 2
40008
Parameter Temperature
Alarm Enable
read/write
word 16 bits
4 = No 5 = Yes
4-5
4-5
40009
Parameter Low
Temperature Alarm
read/write
word 16 bits
Value = X
°C
0°-Par.10
0°-Par.10
See
note 3
40010
Parameter High
Temperature Alarm
read/write
word 16 bits
Value = X
°C
Par.10-120°
Par.10-120°
See
note 4
40011
Parameter Pump
Required
read/write
word 16 bits
4 = No 5 = Yes
4-5
4-5
40012
Parameter Current
Sense Active
read/write
word 16 bits
4 = No 5 = Yes
4-5
4-5
40013
Parameter Alarm Relay
Contact Type
read/write
word 16 bits
0 = Normal Open;
1 = Normal Close
0-1
0-1
40014
Parameter Pump Hours
read/write
word 16 bits
Value = X
h
0-9999
0-9999
40015
Parameter ID Number
read/write
word 16 bits
Value = X
0-99
1-99
40016
Parameter Battery
Activated
read/write
word 16 bits
4 = No 5 = Yes
4-5
4-5
40017
Parameter Expansion
Board Present
read/write
word 16 bits
4 = No 5 = Yes
4-5
4-5
40018
Parameter Minimum
Flow Alarm
read/write
word 16 bits
not used
40019
Parameter Maximum
Flow Alarm
read/write
word 16 bits
not used
40020
Actual Day
read/write
word 16 bits
Value = X
1-31
1-31
40021
Actual Month
read/write
word 16 bits
Value = X
1-12
1-12
40022
Actual Year
read/write
word 16 bits
Value = X
0-99
0-99
40023
Actual Time Hour
read/write
word 16 bits
Value = X
0-23
0-23
40024
Actual Time Minute
read/write
word 16 bits
Value = X
0-59
0-59
40025
Service Date Day
read
word 16 bits
Value = X
1-31
1-31
40026
Service Date Month
read
word 16 bits
Value = X
1-12
1-12
40027
Service Date Year
read
word 16 bits
Value = X
0-99
0-99
40028
Last Serviced Date Day
read
word 16 bits
Value = X
1-31
1-31