Adey FL1-03-06631 Installation And Servicing Download Page 19

19

9. Filtration & Pressure Differential Monitoring

The integrated Grundfos Pressure Differential Sensor, (DPS) and DEK1002 controller 
within these sidestream units monitor the pressure drop across the inlet and outlet of the 

MagnaClean CMX Midi

 filter as the cartridge filters fill-up with captured system debris.

The controller has two preset warning and alarm settings based on debris collection rates within 
the spun-bonded cartridge filters

 used with the 

CMX Midi

 filter. The first ‘warning’ setting sets off an 

audible and visual alarm, warning that the installed cartridges are beginning to fill with debris and that 
a service visit will be required soon. The second ‘alarm’ setting creates an audible and visual alarm, 
warning that the installed cartridges are saturated with system debris, automatically switching off the 
integrated pump. When this alarm function is activated, a service visit is required to clean the internal 
magnet and replace the cartridge filters before the unit can be reset and put back into filtration mode.

For accurate pressure differential monitoring warnings and alarms, cartridge filters must be 
installed in the filter housing;

 the DEK1002 controller does however feature 

programmable magnet-

only service warning alarms

 for when the sidestream skid unit filters are configured with magnets 

only, with no cartridge filters installed. 

These magnet-only warnings are based on time elapsed

 rather 

than differential pressure measurement across the filter, as there is no distinguishable pressure drop 
across the filter without cartridges installed, even when they are full of captured magnetic debris.

These time-based alarms are important as ADEY always recommend that when a 

CMX

  

filter is installed onto an existing heating or chilled system, the filter should initially be 
configured with magnets only.

 This is to ensure that cartridge filters aren’t needlessly wasted 

& blocked with magnetic system debris. The programmable daily, weekly or monthly alarms 
are intended as service reminders which can be easily reset within the controller menu.
After initial set up of the unit, we would recommend a service visit within 24-48 hours to check 
magnetic debris capture levels and service as required. Subsequent service intervals will largely 
depend on the amount of debris being captured. To ensure the unit is able to fully protect and filter the 
system it is installed upon, regular servicing & maintenance of the 

CMX Midi

 filter is recommended.

Once magnetic capture rates begin to reduce, 5, 10, 20 or 50-micron cartridge filters should 
then be installed to capture non-magnetic debris within the system whilst also assisting in the 
capture of any remaining/reoccurring magnetic system debris in conjunction with the internal 
magnet array and where required, the 

CMX Midi External Magnetic Jacket

 accessory.

However, there is no right or wrong way to configure the CMX Midi filter, which can be 
configured with cartridge filters immediately if that is what you believe the system requires. 
Please contact ADEY Customer Services on +44 (0)1242 546717 if you have any queries.

Summary of Contents for FL1-03-06631

Page 1: ...1 MIDI PRO ASSIST MIDI PRO Sidestream Monitored Filtration Installation and servicing MagnaClean CMX Commercial...

Page 2: ...sing with full BMS alarm connectivity these solutions are designed to actively monitor the system and the active filtration of any heating or chilled system in a sidestream configuration for 24 hours...

Page 3: ...Children should be supervised to ensure that they do not play with the appliance Please read installation details carefully as they are intended to ensure this product provides long trouble free servi...

Page 4: ...se sidestream skid units should be installed on a solid level floor which is able to support the filled weight of the unit of c 41 44kg dependent on the model being installed Please also ensure that m...

Page 5: ...flow and temperature sensor based on the principle of vortex shedding behind a bluff body The VFS sensor is fully compatible with wet aggressive liquids constantly monitoring system flow through the...

Page 6: ...t IMPORTANT As this unit is driven by an integrated pump both the unit inlet outlet connections must both be connected to EITHER the main system flow OR the system return as indicated below in Fig 4 T...

Page 7: ...f the unit No special equipment or tools are required for installation This unit can be connected to a heating or chilled system in any location in a sidestream configuration via the two 28mm compress...

Page 8: ...cord Pipework Copper or metallic pipework must have supplementary earth bonding where the continuity has been broken by flexible hoses or plastic components Additional earthing Certain installations m...

Page 9: ...nsure compliance with the electrical standard EN60335 1 It is essential that prior to any disturbance of this internal wiring all cable routing and securing details are carefully noted to ensure re as...

Page 10: ...10 6 Controller Wiring Diagram MagnaClean CMX Midi Pro Assist FL1 03 06632 Fig 6 Controller Wiring Diagram MagnaClean CMX Midi Pro FL1 03 06631 Fig 7...

Page 11: ...re differential across the inlet and outlet of the MagnaClean CMX Midi filter via the integrated Grundfos DPS Sensor providing warning alerts and alarms at two levels Grundfos VFS Flow Sensor a A warn...

Page 12: ...E TIME DATE PROGRAMMING MODE a Press UP Button 1 to increase the value If held will cycle through menu options automatically release button when desired value is achieved b Press DOWN Button 3 to decr...

Page 13: ...asurement Y Y N 7 Low Flow Warning Low Flow warning value 10 0 200L 8 Low Flow Alarm Low Flow alarm value 0 0 200L 9 Sensor Minimum Pressure Maximum pressure value of sensor The default value of 0 0 b...

Page 14: ...on Default Range P1 Cartridge Present Monitors presence of a filter cartridge No Yes No P4 ID Number Address for ModBus 0 0 99 P5 Battery Activation Enable or disable the battery maintains date time s...

Page 15: ...Hours Total pump operation time Auto Update 0 999 1 24 hrs DL4 Current water flow I min Flow rate through sensor at that point in time Auto Update DL5 Water Volume in last 24 hours Amount of water th...

Page 16: ...X 10 Bar Parameter Minimum Pressure 6 0 Parameter Minimum Pressure 60 40011 Parameter Temperature Alarm Enable read write word 16 bits 4 No 5 Yes 44685 00 4 5 40012 Parameter Low Temperature Alarm rea...

Page 17: ...lue X year 0 99 0 99 40043 Actual Hours read write word 16 bits Value X hours 0 23 0 23 40044 Actual Minutes read write word 16 bits Value X min 0 59 0 59 40045 Pump Status read word 16 bits 0 OFF 1 O...

Page 18: ...ol will not clear error until new service date entered Filter Service Required N Pump OFF Buzzer ON LED Light ON Common Alarm ON Low Flow Warning Low flow warning value has been reached Low Flow Warni...

Page 19: ...sure measurement across the filter as there is no distinguishable pressure drop across the filter without cartridges installed even when they are full of captured magnetic debris These time based alar...

Page 20: ...n 3 4 2 Chemical dosing facilities BG29 2021 Section 2 3 8 and BG50 2021 Section 3 4 3 Corrosion monitoring technology and services BG 29 2021 Section 2 3 8 The additional features of these products a...

Page 21: ...s at the top of the unit to isolate the filter from the main system 5 Undo the wing nut remove the compression plate Carefully remove the magnet assembly from the filter 8 Place the springs into the t...

Page 22: ...ensuring that the lid gasket is positioned and installed correctly Re attach the lid clamp and tighten 11 Ensure filter drain port valve s are closed and then open both isolation valves at the top of...

Page 23: ...ce free However it might be necessary to deblock or to open the pump for example if it is blocked by impurities De blocking is possible by opening the de blocking screw at the front 1 Unscrew the de b...

Page 24: ...utlet 28mm compression Isolation Valves Pump Pump model Grundfos UPM3 FLEX AS 25 70 130 Pump type Circulation PWM A Pump head material Electrocoated Cast Iron Impeller material Composite PES 30 GF Min...

Page 25: ...ture Min 2 C Max 40 C Min Max water temperature Min 2 C Max 100 C Connections Inlet outlet 28mm compression Isolation Valves System Monitoring Differential Pressure Sensor Grundfos DPS Sensor Vortex F...

Page 26: ...ce interval date Pump is blocked with impurities Unblock the pump and remove impurities Pump is defective Replace pump contact ADEY Customer Services PUMP RUNS AT MAX SPEED CANNOT BE CONTROLLED No sig...

Page 27: ...y is defined by the sequence of the table Operating Panel LED1 LED2 LED3 LED4 LED5 Indication Pump Operation Remedy Rotor is blocked Trying to start again every 1 33 seconds Wait or unblock the rotor...

Page 28: ...of the declaration have been designed manufactured in accordance with Regulation 8 Paragraph 2 of Pressure Equipment Safety Regulations 2016 The product s also comply with the requirements of the WEE...

Page 29: ...29...

Page 30: ...30...

Page 31: ...31...

Page 32: ...ADEY Commercial Ltd Unit 2 St Modwen Park Stonehouse GL10 3EZ Produced from recycled material A carbon neutral company All ADEY marks are trademarks of Adey Holdings 2008 Limited Please visit adey co...

Reviews: