PARAMETER PROGRAMMING MODE - ENGINEERS PARAMETER MENU
(Code: 315)
#
Parameter
Description
Default
Range
-
Service Date
Adjust future service date: Day/Month/Year. Press
& hold ‘SET to cycle across values. Will pass onto
next parameter once complete
-
-
-
Last Service Date
Automatically updates when a new service date
has been entered and will be visible next time user
accesses parameters
-
-
1
Cartridge*
Present
Monitors presence of a filter cartridge
No
Yes/No
2
Magnet Only**
Service Warning
Daily/weekly/monthly warning alarm
Daily
Daily
Weekly
Monthly
3
Magnet Only
Service Warning
Duration
Number of days/weeks/months (unit representation
dependent upon Parameter 2 Alarm choice - Daily,
Weekly or Monthly)
2
1-12
4
Pressure
Difference
Warning
Warning trigger point based on pressure
differential output
(The default value of 0.4 bar
should not be changed)
0.4
0.1 - 2.5 bar
5
Pressure
Difference Alarm
Alarm trigger point based on pressure differential
output
(The default value of 0.6 bar should not be
changed)
0.6
0.1 - 2.5 bar
6
Flow Monitoring
Enable
Enables/disables flow monitoring & measurement
Y
Y/N
7
Low Flow Warning
Low Flow warning value
10
0 - 200L
8
Low Flow Alarm
Low Flow alarm value
0
0 - 200L
9
Sensor Minimum
Pressure
Maximum pressure value of sensor
(The default
value of 0.0 bar should not be changed)
0.0 bar
0 - 2.5 bar
10
Sensor Maximum
Pressure
Maximum pressure value of sensor
(The default
value of 2.5 bar should not be changed)
2.5 bar
0 - 2.5 bar
11
Temperature
Alarm Enable
Enables/disables temperature alarm
Yes
Yes/No
12
Low Temperature
Alarm
Low temperature alarm value
4°C
0 - 120°C
13
High Temperature
Alarm
High temperature alarm value
90°C
0 - 120°C
14
Pump Required
Disables activation of pump relay. If set to NO, Current
Sense (Parameter 13) will auto NO; When set to YES,
Current Sense (Parameter 13) will auto YES
Yes
Yes/No
15
Current Sense
Monitors current for presence of pump
Yes
Yes/No
16
Alarm Relay
Contact
Type of Contact for Alarm Output (NO= Relay in
open position; closes on alarm; NC = Relay in closed
position; opens on alarm)
No
No/NC
17
ID Number
Address for Mod Bus
0
0 - 99
18
Pump Hours
Total Operation Hours for Pump (Auto Update)
0 - 999
1 = 24 hrs
19
Battery Activation
Enable or disable the Battery (Maintains date and
time settings if power is lost to the controller - on
first power up battery will automatically activate)
No
Yes/No