1
MIDI PRO ASSIST &
MIDI PRO
Sidestream Monitored Filtration
Installation and servicing
MagnaClean CMX
®
Commercial
Page 1: ...1 MIDI PRO ASSIST MIDI PRO Sidestream Monitored Filtration Installation and servicing MagnaClean CMX Commercial...
Page 2: ...sing with full BMS alarm connectivity these solutions are designed to actively monitor the system and the active filtration of any heating or chilled system in a sidestream configuration for 24 hours...
Page 3: ...Children should be supervised to ensure that they do not play with the appliance Please read installation details carefully as they are intended to ensure this product provides long trouble free servi...
Page 4: ...se sidestream skid units should be installed on a solid level floor which is able to support the filled weight of the unit of c 41 44kg dependent on the model being installed Please also ensure that m...
Page 5: ...flow and temperature sensor based on the principle of vortex shedding behind a bluff body The VFS sensor is fully compatible with wet aggressive liquids constantly monitoring system flow through the...
Page 6: ...t IMPORTANT As this unit is driven by an integrated pump both the unit inlet outlet connections must both be connected to EITHER the main system flow OR the system return as indicated below in Fig 4 T...
Page 7: ...f the unit No special equipment or tools are required for installation This unit can be connected to a heating or chilled system in any location in a sidestream configuration via the two 28mm compress...
Page 8: ...cord Pipework Copper or metallic pipework must have supplementary earth bonding where the continuity has been broken by flexible hoses or plastic components Additional earthing Certain installations m...
Page 9: ...nsure compliance with the electrical standard EN60335 1 It is essential that prior to any disturbance of this internal wiring all cable routing and securing details are carefully noted to ensure re as...
Page 10: ...10 6 Controller Wiring Diagram MagnaClean CMX Midi Pro Assist FL1 03 06632 Fig 6 Controller Wiring Diagram MagnaClean CMX Midi Pro FL1 03 06631 Fig 7...
Page 11: ...re differential across the inlet and outlet of the MagnaClean CMX Midi filter via the integrated Grundfos DPS Sensor providing warning alerts and alarms at two levels Grundfos VFS Flow Sensor a A warn...
Page 12: ...E TIME DATE PROGRAMMING MODE a Press UP Button 1 to increase the value If held will cycle through menu options automatically release button when desired value is achieved b Press DOWN Button 3 to decr...
Page 13: ...asurement Y Y N 7 Low Flow Warning Low Flow warning value 10 0 200L 8 Low Flow Alarm Low Flow alarm value 0 0 200L 9 Sensor Minimum Pressure Maximum pressure value of sensor The default value of 0 0 b...
Page 14: ...on Default Range P1 Cartridge Present Monitors presence of a filter cartridge No Yes No P4 ID Number Address for ModBus 0 0 99 P5 Battery Activation Enable or disable the battery maintains date time s...
Page 15: ...Hours Total pump operation time Auto Update 0 999 1 24 hrs DL4 Current water flow I min Flow rate through sensor at that point in time Auto Update DL5 Water Volume in last 24 hours Amount of water th...
Page 16: ...X 10 Bar Parameter Minimum Pressure 6 0 Parameter Minimum Pressure 60 40011 Parameter Temperature Alarm Enable read write word 16 bits 4 No 5 Yes 44685 00 4 5 40012 Parameter Low Temperature Alarm rea...
Page 17: ...lue X year 0 99 0 99 40043 Actual Hours read write word 16 bits Value X hours 0 23 0 23 40044 Actual Minutes read write word 16 bits Value X min 0 59 0 59 40045 Pump Status read word 16 bits 0 OFF 1 O...
Page 18: ...ol will not clear error until new service date entered Filter Service Required N Pump OFF Buzzer ON LED Light ON Common Alarm ON Low Flow Warning Low flow warning value has been reached Low Flow Warni...
Page 19: ...sure measurement across the filter as there is no distinguishable pressure drop across the filter without cartridges installed even when they are full of captured magnetic debris These time based alar...
Page 20: ...n 3 4 2 Chemical dosing facilities BG29 2021 Section 2 3 8 and BG50 2021 Section 3 4 3 Corrosion monitoring technology and services BG 29 2021 Section 2 3 8 The additional features of these products a...
Page 21: ...s at the top of the unit to isolate the filter from the main system 5 Undo the wing nut remove the compression plate Carefully remove the magnet assembly from the filter 8 Place the springs into the t...
Page 22: ...ensuring that the lid gasket is positioned and installed correctly Re attach the lid clamp and tighten 11 Ensure filter drain port valve s are closed and then open both isolation valves at the top of...
Page 23: ...ce free However it might be necessary to deblock or to open the pump for example if it is blocked by impurities De blocking is possible by opening the de blocking screw at the front 1 Unscrew the de b...
Page 24: ...utlet 28mm compression Isolation Valves Pump Pump model Grundfos UPM3 FLEX AS 25 70 130 Pump type Circulation PWM A Pump head material Electrocoated Cast Iron Impeller material Composite PES 30 GF Min...
Page 25: ...ture Min 2 C Max 40 C Min Max water temperature Min 2 C Max 100 C Connections Inlet outlet 28mm compression Isolation Valves System Monitoring Differential Pressure Sensor Grundfos DPS Sensor Vortex F...
Page 26: ...ce interval date Pump is blocked with impurities Unblock the pump and remove impurities Pump is defective Replace pump contact ADEY Customer Services PUMP RUNS AT MAX SPEED CANNOT BE CONTROLLED No sig...
Page 27: ...y is defined by the sequence of the table Operating Panel LED1 LED2 LED3 LED4 LED5 Indication Pump Operation Remedy Rotor is blocked Trying to start again every 1 33 seconds Wait or unblock the rotor...
Page 28: ...of the declaration have been designed manufactured in accordance with Regulation 8 Paragraph 2 of Pressure Equipment Safety Regulations 2016 The product s also comply with the requirements of the WEE...
Page 29: ...29...
Page 30: ...30...
Page 31: ...31...
Page 32: ...ADEY Commercial Ltd Unit 2 St Modwen Park Stonehouse GL10 3EZ Produced from recycled material A carbon neutral company All ADEY marks are trademarks of Adey Holdings 2008 Limited Please visit adey co...