background image

— 55 —

TRANSFORMER

W/ENCLOSURE

(lower left corner of cabinet)

REPLACE COVER AFTER

See instructions for 
proper earth ground 
connections

ZONE 2

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

+

SMOKE

2-WIRE SMOKE

DETECTOR LOOP

                                       

N.C.

N.O.

2k (Note 2)

+

+

N.C.

2k 

N.O.

GLASS
BREAK

 

REMOTE KEYPADS:

6139, 6139R
(See Note 3)

Red

Blk

Grn

Yel

Data in

Data out

+

4209U

4208U

2-WIRE GLASS BREAK

DETECTOR LOOP

4192SD
SMOKE

BACK-UP LINE SEIZE

LED (GREEN)

Connect to main PCB
header J3 using ribbon 
cable (supplied)

BACK-UP DIALER ON HOOK
VOLTAGE THRESHOLD (BLUE)
INTACT: 25V
CUT: 13V

OPTIONAL 5140DLM BACK-UP DIALER MODULE

MAIN PCB SHIELD

BACK-UP PHONE JACK
SEE TELCO 
JACK SHOCK  
WARNING 
BELOW

J2

Make connections using

4142TR cable (not supplied)

VOLTAGE 
TRIGGERS

(not supervised)

J3

1    2   3   4    5    6   7   8    9

J4

Make connections using 
4142TR cable (supplied)

(not supervised)

KEYPAD PORT #2

BELL 1

W1

(WHITE)

BELL 2

W4

(WHITE)

BELL CIRCUIT SUPERVISION JUMPERS
  INTACT: Supervised using 2k EOLR
  CUT: Not supervised (no EOLR used)

BLK           +    RED 

OPTIONAL REMOVABLE
TERMINAL BLOCK KIT:
 
ADEMCO NO. 4142BLK

BELL

HORN

BELL

HORN

+

SMOKE

N.C.

N.O.

2k 

+

N.C.

N.O.

+

N.C.

N.O.

+

N.C.

N.O.

+

N.C.

N.O.

+

N.C.

N.O.

TO OTHER DEVICES

2k 2k  2k 2k  2k 

ZONE 1

ZONE 3

ZONE 4

ZONE 5

ZONE 6

ZONE 7

ZONE 8

NOTE 3:

See instructions on setting 
addresses & for max # of keypads
and wire run length restrictions. 
Keypad color subject to approval 
of local authority.

+

2k (Note 2) 

2k 

AC WIRING IS 
SUPERVISED

BELL 1

BELL 2

+

+

ALARM POLARITY SHOWN

Each output may be selected for 
Style Y supervision or no supervision
(See main PCB jumpers W1, W4 and
zone 970, 971, programming.
FIRE CKTS:  Supervise using 2k EOLR. 
Use polarized sounding devices.
BURG CKTS: Supervision not req'd. 
EOLRs not req'd. May use non 
polarized devices.
Ratings: 10 - 14VDC, 1.7A max. 
See note 1, see instructions 
for compatible devices.

N

.O

.

POLE

N.C.

AUX RELAY (FORM C)
programmable response
(not supervised)
Contact Rating:
28V, 2.8A
resistive loads

SPARE AUX 

POWR #1

AUXILIARY POWER #1
Rating: 10 - 14VDC
1.0A MAX (STANDBY)
1.7A MAX (ALARM)
See Note 1.
(not supervised) 

NOTE 1:

The combined standby current 
drawn from aux pwr #1, aux pwr #2
and polling loop cannot exceed 
1.0A.The combined alarm current
drawn from aux pwr #1, aux 
pwr #2, polling loop, bell 1 and
bell 2 cannot exceed 2.3A.

2-W

IRE SMOKE

DETECTOR LOOP

                                       

P

R

O

G

R

A

M

M

A

B

L

E

A

S

 T

A

M

P

E

R

 L

O

O

P

                                       

P

R

O

G

R

A

M

M

A

B

L

E

A

S

 K

E

Y

 S

W

IT

C

H

 L

O

O

P

                                       

ZONE 1-8 NOTES
  All zones provide Style B supervision
  Zone resistance (excluding EOLR):
   - Zones 1, 2, 8: 100 ohms  max
   - Other zones: 300 ohms  max
  Zone response: 350 - 500mS (all zones)

Connect to 12V, 7AH min/34.4AH max
lead acid batteries using cables supplied. 
See instructions for required capacity.
Float charging voltage: 13.7VDC. Battery
normally need not be replaced for
at least 3 yrs.

VISTA-32FB SUMMARY OF CONNECTIONS

J4 KEYPAD PORT #2
See instr. regarding port #2 use
1. GROUND (to keypad black wire)
4. DATA IN 2 (to keypad green wire)
5. AUX PWR #2 (to keypad red wire)
    Rating: 10 - 14 VDC, 
    400mA max. See note 1 
7. DATA OUT 2 (to keypad yellow wire)

W6

(BLUE)

INTERFACE TO 5140DLM

MAIN DIALER ON HOOK
VOLTAGE THRESHOLD 
INTACT:25V
CUT: 13V

BACK-UP DIALER EARTH 
GROUND SCREW 
(wire to main PCB
terminal #30)

J2 VOLTAGE TRIGGERS
See instructions for trigger use and programming
              (default functions shown)
1. OUT 4 (SILENT PANIC/DURESS)
2. OUT 7 (TROUBLE)
3. OUT 3 (BURGLARY/AUDIBLE PANIC)
4. OUT 6 (SUPERVISORY)
5. OUT 2 (FIRE)
6. OUT 5 (REMOTE KEYPAD SOUNDER)
7. OUT 1 (OPEN/CLOSE)
8. GROUND
9. IN 1 (N.O. LOOP)
RATINGS: OUT 1, 5, 7:  
                          LOW: 2K TO GROUND
                          HIGH: 10 - 14VDC, 20mA MAX
OTHER OUTS: LOW: 1K TO GROUND
                           HIGH: 10 - 14VDC THRU  5K

Attach 5140DLM module to main PCB shield using 
4 standoffs (supplied)

1    2   3   4    5    6   7   8    9

REFER TO INSTRUCTIONS K3521 FOR ADDITIONAL INFORMATION

WARNING: OWNER'S INSTRUCTION NOTICE NOT TO BE REMOVED

BATTERY TABS

 PINS 2, 3, 6, 8  & 9 NOT USED

RJ31X

MAIN

PHONE JACK

BELL OUTPUTS

AUX. RELAY

KEYPAD PORT #1

NOTE 2:

2k EOLR is Ademco model 610-7

CONNECTION OF THE  FIRE ALARM
SIGNAL TO A FIRE ALARM HEAD-
QUARTERS OR A CENTRAL STATION
SHALL BE PERMITTED ONLY WITH
THE APPROVAL OF THE LOCAL
AUTHORITY HAVING JURISDICTION.
THE  BURGLARY ALARM SIGNAL 
SHALL NOT BE CONNECTED TO A 
POLICE EMERGENCY NUMBER.

POLLING 

LOOP

WARNING: 
TO PREVENT
RISK OF 
ELECTRICAL
SHOCK,
DISCONNECT
TELCO JACK
BEFORE 
SERVICING
THIS PANEL

Connect 
RJ31X using 
cable supplied. 
Supervision is 
programmable

TYPES OF FIRE SIGNALLING SERVICE:
Manual fire alarm, automatic fire alarm, sprinkler supervisory and waterflow alarm. UL Listed local control (non-coded). 
UL Listed central station and remote station protected premises unit when used with 5140DLM back-up dialer module.
Installation limits under jurisdiction of local authority. 

CIRCUIT

(ZONE)

CONTROL UNIT

DELAY-SEC

SMOKE DETECTOR

MODEL   DELAY-SEC

THE DELAY TIME MARKED ON THE INSTALLED 
DETECTOR(S) IS TO BE USED

Polling Loop Ratings:  (supervised)
128mA max. See Note 1.
See instructions for compatible devices
and for max wire run length

BL

BL

BLACK

WHITE

RJ31X

 (connect using supplied cable)

Supervision is programmable

EARTH GROUND

  Ratings for zones 1,2:
  - 10 - 14VDC
  - 2mA max for smoke det. (up to 16 detectors 
    of the type specified in the instructions 
     can be used)

UL compatibility ID: A
Do not mix fire and burg. sensors on one loop.
N.C. contacts for burg. usage only.

NOTES

TRNSFMR

ALL CIRCUITS ARE POWER LIMITED EXCEPT 
THE OUTPUT OF THE POWER TRANSFORMER

TEST BURGLARY SYSTEM WEEKLY

The VISTA-32FB Main Dialer

Complies with FCC Rules, Part 68

FCC Reg. No.: AC398U-68192-AL-E

Ringer Equivalence: 0.7B

The 5140DLM Dialer

Complies with FCC Rules, Part 68

FCC Reg. No.: AC398U-68628-MO-N

Ringer Equivalence: 0.7B

WARNING:
THIS UNIT MAY BE PROGRAMMED TO 
INCLUDE AN ALARM VERIFICATION 
FEATURE THAT WILL RESULT IN A DELAY
OF THE SYSTEM ALARM SIGNAL FROM 
THE INDICATED FIRE CIRCUITS. THE 
TOTAL DELAY (CONTROL UNIT PLUS 
SMOKE DETECTORS) SHALL NOT EXCEED 
60 SECONDS. NO OTHER INITIATING 
DEVICES SHALL BE CONNECTED TO 
THESE CIRCUITS UNLESS APPROVED BY 
THE LOCAL AUTHORITY HAVING
JURISDICTION.

THIS EQUIPMENT 
SHOULD BE INSTALLED 
IN ACCORDANCE WITH 
THE NATIONAL FIRE 
PROTECTION ASSOC-
IATION'S STANDARD 72 
(NATIONAL FIRE 
PROTECTION ASSOC., 
BATTERYMARCH PARK, 
QUINCY, MA. 02269). 
PRINTED INFORMATION 
DESCRIBING PROPER 
INSTALLATION, 
OPERATION, TESTING, 
MAINTENANCE AND
REPAIR SERVICE IS 
TO BE PROVIDED WITH 
THIS EQUIPMENT.

For commercial fire, bell timeout
must be a minimum of 6 minutes. 

NOTE:  Use wires that
have insulation rated
for 90

˚

c or higher.

GRN

OUTPUT: 18VAC, 72VA

Not Power Limited

Maintain 1/4" spacing

to other wire

Connect to
Earth Ground
Terminal 30

INPUT:

120VAC, 60HZ,

1.0A max. 

Connect to a

dedicated circuit.

Connect to 

Proper Earth
Ground. See

instructions.

GRN

Assembled In

Mexico

NOTE:  As shipped,
Vista-32FB is suitable
for UL Commercial Fire
Installations.  Cabinet
supports up to 14AH
Batteries.  Use Vista-ULKT
Cabinet Kit to house 
up to 34.4AH Batteries.
Also use this kit along
with 1451 Transformer
for UL Listed Commercial
Burglary Installations.

2A Circuit

Breaker

www.PDF-Zoo.com

Summary of Contents for VISTA-32FB

Page 1: ...K3840V1 9 00 9 9 6 67 7 RPPHUFLDO LUH DQG XUJODU 3DUWLWLRQHG 6HFXULW 6 VWHP ZLWK 6FKHGXOLQJ 3URJUDPPLQJ XLGH FIRE FIRE PULL www PDF Zoo com...

Page 2: ...ne alpha keypad is connected to the control and is set to device address 00 Single Partition System The system default is for a single partition system Use the VISTA 32FB SINGLE PARTITION PROGRAMMING...

Page 3: ...eway Module 6 Use 93 Menu Mode for zone programming Refer to the Zone Programming in this guide to program zone response types assign right loop zones and wireless zones assign zones to partitions and...

Page 4: ...Communications 90 Partition Specific 1 01 93 Menu Mode 1 02 93 Menu Mode 1 03 93 Menu Mode 1 04 93 Menu Mode 1 05 93 Menu Mode 1 06 93 Menu Mode 1 07 93 Menu Mode 1 08 93 Menu Mode 1 09 93 Menu Mode 1...

Page 5: ...hrs 0 normal report about 2 min after AC loss Must be 2 for Central and Remote Station Fire alarm systems 20 VIP MODULE PHONE CODE Enter 01 09 for the first digit enter 00 11 11 for or 12 for for the...

Page 6: ...go to secondary only If used with Split Reporting 2 option alarms and alarm restores go to both open close and test messages go to secondary only while all other reports go to primary If used with Spl...

Page 7: ...ial Fire UL installations 1 19 ARMS LOBBY 0 Enter 1 if arming this partition attempts to arm lobby enter 0 if it does not Must be 0 for Commercial Fire UL installations 1 20 EXIT ERROR LOGIC 0 0 No 1...

Page 8: ...es of 2 minutes desired for 80 Menu Mode time driven event relay command numbers 04 09 and 93 Menu Mode Output Programming command 56 1 75 RELAY TIMEOUT YY SECONDS 000 Enter the relay timeout 0 127 se...

Page 9: ...waterflow restores 3 15 ALARM BELL SOUND 1 0 0 pulsed 1 steady Bell 1Bell 2 3 16 DELAY for ZONE TYPES 17 18 00 Waterflow FIre Supv Enter 00 15 times 2 seconds 3 17 ALTERNATE FUNCTION TAMPER 0 FOR ZONE...

Page 10: ...r UL Commercial Burglary installations 12 EXIT DELAY 2 08 00 15 times 15 seconds Maximum 04 for UL Commercial Burglary installations 13 BELL 1 TIMEOUT 04 01 15 times 2 minutes Minimum 16 minutes for U...

Page 11: ...enings and closings occurring outside the scheduled opening closing windows will trigger dialer reports Opening reports will also be suppressed during the closing window in order to prevent false repo...

Page 12: ...lows ZONE PROG 1 YES 0 NO For programming the following Zone Number Zone Response Type Partition Number for Zone Dialer report code for zone Bell aux relay assignment for zone Input Device Type for zo...

Page 13: ...screen Press to display a previous screen SET TO CONFIRM 0 NO 1 YES 0 This prompt will appear once upon entering Zone Programming If Yes Confirmation prompts will be displayed after the device s Seri...

Page 14: ...nd 12 for C Refer to System Communication section for more information about report codes and report code formats Press to continue 010 INPUT TYPE RF Xmitter 3 Note that input types 4 5 are valid for...

Page 15: ...ess and release the button a second time OR b Manually enter the 7 digit serial number printed on a label on the transmitter using the Alpha keypad Then press the key the cursor will move to the L pos...

Page 16: ...HOUSE CODE YOU MUST ENROLL THIS BUTTON LOOP 1 5809 ENROLL AS RF 5801 ENROLL AS UR OR RF LOOP 3 LOOP 1 LOOP 2 LOOP 4 YOU MUST ENROLL THIS BUTTON Note For information on any transmitter not shown above...

Page 17: ...est each using the system s Test Mode Do not use the Transmitter ID Sniffer Mode for this The system will check only for transmission of one zone on a particular transmitter NOT the zones assigned to...

Page 18: ...reen Use the A key to move to the right Use the B key to move to left and to back up to B field Press to accept existing information 010 INPUT S N L A XXX XXXX If you entered RF BR UR or SL for the In...

Page 19: ...e type etc relevant to that device Entering Wireless Keys If the D key was previously pressed to enter defaults for 5804 and or 5804BD wireless keys the following screens will appear FROM TEMPLATE 1 6...

Page 20: ...Zone No prompt and will show the lowest numbered zone of the next available 4 zone group consecutive zones that is available for programming When all zones have been programmed enter 000 to quit Afte...

Page 21: ...tem will be entered at one time In actuality it is possible to skip from one main menu option to another by pressing 0 NO at each main menu option Main menu options are highlighted in bold text To ent...

Page 22: ...016 00 Enter the first digit of the Bypass Restore Report Code double digit entry and press The second digit for two digit reporting formats is automatically the ID second digit of the Alarm Report Co...

Page 23: ...number is desired as the second digit enter 01 not necessary for Contact ID or High Speed formats Press to continue Enter the rest of the codes in the same manner Other codes in System Group 3 are Ear...

Page 24: ...ck to 93 Menu Mode 4 Refer to the sections that follow for procedures for adding alpha descriptors Zone Descriptors 1 Select ZONE DESCRIPTOR mode The keypad keys perform the following functions 3 Scro...

Page 25: ...hat there are only 16 character spaces on each of the two lines To create a custom display message proceed as follows 1 Select Default Screen Mode The keypad will ask for the partition number for this...

Page 26: ...s 3 to advance through the list of symbols numbers and letters Press 1 to move back through the list When the desired character has been reached press 6 to select it The cursor will then move to the r...

Page 27: ...MEDICAL 135 MEDICINE 136 MICROWAVE 137 MONEY 138 MONITOR 139 MOTHERS 140 MOTION 141 MOTOR 142 MUD 143 NORTH 144 NURSERY 145 OFFICE 146 OIL 147 OPEN 148 OPENING 149 OUTSIDE 150 OVERFLOW 151 OVERHEAD 15...

Page 28: ...er 01 to maximum number of partitions programmed for system in field 2 00 This is the primary partition for which the device is intended to be used Enter 9 to make this keypad a master keypad for the...

Page 29: ...Key Normal Key Function SHIFT Key Function BS ESC BS Press to delete entry ESC Press to quit Program Mode Also can reset EEPROM defaults Scroll down programming Scroll up programming N Y N Press for N...

Page 30: ...F will not be displayed for private system users BAT PRESENT Y N N Enter Y if optional battery will be used Must be Y for UL installations a battery must be installed USE RADIO Y N N If Y is selected...

Page 31: ...ere are no other zones of this type which are not to activate this device then ZONE TYPE may be used instead of using a ZONE LIST and EVENT to activate the device If a System Operation such as DISARMI...

Page 32: ...List or Zone Type System Operation combination to start the Output action Enter the 3 digit zone number Press to continue 02 START ZN TYPE NO RESPONSE 00 A Zone Type System Operation can be used inst...

Page 33: ...OUTPUT GROUP 00 Outputs may be grouped for common activation by time driven events commands 06 10 Enter 00 no group or 01 15 for a specific group number Press to continue 02 RESTRICTION 1 YES 0 NO 0 T...

Page 34: ...more zones in that zone list Enter 0 if no changes are necessary If 1 is entered the following screen will appear otherwise the Enter Zone LIST prompt will reappear 01 Zn to DELETE 000 QUIT 000 Enter...

Page 35: ...r 116 Alarm 255 And 067 Apartment 117 Appliances 161 Area 118 Attic 119 Baby 120 Back 121 Bar 122 Basement 021 Bathroom 051 Battery 053 Bed 092 Bedroom 015 Blower 123 Boiler 124 Bright 162 Building 12...

Page 36: ...ress to accept entry The CUSTOM WORD NO prompt will be displayed Enter the next custom word number to be substituted or enter 00 to quit System Layout Worksheets As with any security system you should...

Page 37: ...ion During Entry Console Annunciation During Exit Confirmation of Arming Ding for Bell 1 Confirmation of Arming Ding for Bell 2 Aux Rly Chime on Bell 1 Chime on Bell 2 Aux Relay Access Control Relay f...

Page 38: ...d Entry Exit Beeps 02 Suppress Chime Mode Beeps Only 03 Suppress Arm Disarm Entry Exit and Chime Mode Beeps Defaults Addresses 00 01 Alpha Keypad No Suppression ACCESS CODES USER DEFINITIONS FOR PARTI...

Page 39: ...Parti tion 1 2 Input Type 1 13 Serial Device Loop Bell Relay Activation Report Code Zone Information part numbers Alpha Descriptor 3 words max 01 02 03 04 05 06 07 08 09 010 011 012 013 014 015 016 01...

Page 40: ...31 032 ZONE DEFINITIONS FOR KEYPAD PANIC ZONES 995 996 999 Enter yes no for each partition field 22 Zone No Zone Type 1 2 Bell Rel Act Report Code Zone Information part numbers Alpha Descriptor 3 word...

Page 41: ...9 602 610 603 611 604 612 605 613 606 614 607 615 608 616 ZONE DEFINITIONS FOR SUPERVISORY OF ECP DEVICE ZONES 800 831 Zone No Zone Type Report Code Zone Information part numbers Alpha Descriptor 3 wo...

Page 42: ...ght burglary 29 Momentary on exit Input Types 00 not used 08 right loop dip switch polling loop 01 hardwired 09 keypad input 03 supervised RF transmitter 10 PassPoint ACS input 04 unsupervised RF tran...

Page 43: ...ation instructions as you enter the data during the displays and prompts that appear in sequence Notes For 4204 4204CF and FSA the Device Programming section must be programmed for the device address...

Page 44: ...S T O P OUTPUT DEV A EV ZL Zone ZT P ZL ZT P Output Group Restrict 0 V Plex 1 4204 3 FSA V Plex Zone or Dev Add 4204 or FSA Relay for 4204 or LED for FSA 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35...

Page 45: ...S T O P OUTPUT DEV A EV ZL Zone ZT P ZL ZT P Output Group Restrict 0 V Plex 1 4204 3 FSA V Plex Zone or Dev Add 4204 or FSA Relay for 4204 or LED for FSA 46 47 48 49 50 51 52 53 54 55 56 57 58 59 61...

Page 46: ...S T O P OUTPUT DEV A EV ZL Zone ZT P ZL ZT P Output Group Restrict 0 V Plex 1 4204 3 FSA V Plex Zone or Dev Add 4204 or FSA Relay for 4204 or LED for FSA 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86...

Page 47: ...ght 29 Momentary on Exit 54 Fire Zone Reset 06 24 Hr Silent 30 On Second Code Off 55 Disarm 1 Minute 07 24 Hr Audible 31 End of Exit Time 08 24 Hr Auxiliary 32 Start of Entry Time 56 XX Minutes enter...

Page 48: ...Zone List 1 Started or stopped by zone numbers enter 000 to end entries Zone List 2 Started or stopped by zone numbers enter 000 to end entries Zone List 3 Started or stopped by zone numbers enter 00...

Page 49: ...r 000 to end entries Zone List 12 Started or stopped by zone numbers enter 000 to end entries Zone List 13 Started or stopped by zone numbers enter 000 to end entries Zone List 14 Started or stopped b...

Page 50: ...window for each day of the week and holidays Holidays 1 Yes 0 No 0 For defining up to 16 holidays for which partitions they apply Timed Events 1 Yes 0 No 0 For defining up to 20 time driven events wi...

Page 51: ...17 18 19 20 Keep this worksheet handy as you will be asked for a given time window number later in this section Since the time windows are shared among all partitions it is important to make sure that...

Page 52: ...r in sequence HOL Partition Month Day 1 2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Time Driven Event Worksheet The system provides up to 20 time driven events that can be programmed for the system Fill...

Page 53: ...lose Windows Action Specifier for commands 40 41 is Partition s for 42 is Access Group and for 50 no specifier is programmed Activation time 3 During is the only valid choice for these commands 40 Ena...

Page 54: ...4 5 6 7 8 Temporary Schedule 81 Menu Mode The system provides a Temporary Schedule for each partition Enter the temporary scheduling mode by pressing Installer Code 81 Fill in the required data on the...

Page 55: ...ERVISORY 5 OUT 2 FIRE 6 OUT 5 REMOTE KEYPAD SOUNDER 7 OUT 1 OPEN CLOSE 8 GROUND 9 IN 1 N O LOOP RATINGS OUT 1 5 7 LOW 2K TO GROUND HIGH 10 14VDC 20mA MAX OTHER OUTS LOW 1K TO GROUND HIGH 10 14VDC THRU...

Page 56: ...9 l K3840V1 9 00 165 Eileen Way Syosset NY 11791 Copyright 2000 PITTWAY Corporation www PDF Zoo com...

Reviews: