— 55 —
TRANSFORMER
W/ENCLOSURE
(lower left corner of cabinet)
REPLACE COVER AFTER
See instructions for
proper earth ground
connections
ZONE 2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
+
SMOKE
2-WIRE SMOKE
DETECTOR LOOP
N.C.
N.O.
2k (Note 2)
+
+
N.C.
2k
N.O.
GLASS
BREAK
REMOTE KEYPADS:
6139, 6139R
(See Note 3)
Red
Blk
Grn
Yel
Data in
Data out
+
4209U
4208U
2-WIRE GLASS BREAK
DETECTOR LOOP
4192SD
SMOKE
BACK-UP LINE SEIZE
LED (GREEN)
Connect to main PCB
header J3 using ribbon
cable (supplied)
BACK-UP DIALER ON HOOK
VOLTAGE THRESHOLD (BLUE)
INTACT: 25V
CUT: 13V
OPTIONAL 5140DLM BACK-UP DIALER MODULE
MAIN PCB SHIELD
BACK-UP PHONE JACK
SEE TELCO
JACK SHOCK
WARNING
BELOW
J2
Make connections using
4142TR cable (not supplied)
VOLTAGE
TRIGGERS
(not supervised)
J3
1 2 3 4 5 6 7 8 9
J4
Make connections using
4142TR cable (supplied)
(not supervised)
KEYPAD PORT #2
BELL 1
W1
(WHITE)
BELL 2
W4
(WHITE)
BELL CIRCUIT SUPERVISION JUMPERS
INTACT: Supervised using 2k EOLR
CUT: Not supervised (no EOLR used)
BLK + RED
OPTIONAL REMOVABLE
TERMINAL BLOCK KIT:
ADEMCO NO. 4142BLK
BELL
HORN
BELL
HORN
+
SMOKE
N.C.
N.O.
2k
+
N.C.
N.O.
+
N.C.
N.O.
+
N.C.
N.O.
+
N.C.
N.O.
+
N.C.
N.O.
TO OTHER DEVICES
2k 2k 2k 2k 2k
ZONE 1
ZONE 3
ZONE 4
ZONE 5
ZONE 6
ZONE 7
ZONE 8
NOTE 3:
See instructions on setting
addresses & for max # of keypads
and wire run length restrictions.
Keypad color subject to approval
of local authority.
+
2k (Note 2)
2k
AC WIRING IS
SUPERVISED
BELL 1
BELL 2
+
+
ALARM POLARITY SHOWN
Each output may be selected for
Style Y supervision or no supervision
(See main PCB jumpers W1, W4 and
zone 970, 971, programming.
FIRE CKTS: Supervise using 2k EOLR.
Use polarized sounding devices.
BURG CKTS: Supervision not req'd.
EOLRs not req'd. May use non
polarized devices.
Ratings: 10 - 14VDC, 1.7A max.
See note 1, see instructions
for compatible devices.
N
.O
.
POLE
N.C.
AUX RELAY (FORM C)
programmable response
(not supervised)
Contact Rating:
28V, 2.8A
resistive loads
SPARE AUX
POWR #1
AUXILIARY POWER #1
Rating: 10 - 14VDC
1.0A MAX (STANDBY)
1.7A MAX (ALARM)
See Note 1.
(not supervised)
NOTE 1:
The combined standby current
drawn from aux pwr #1, aux pwr #2
and polling loop cannot exceed
1.0A.The combined alarm current
drawn from aux pwr #1, aux
pwr #2, polling loop, bell 1 and
bell 2 cannot exceed 2.3A.
2-W
IRE SMOKE
DETECTOR LOOP
P
R
O
G
R
A
M
M
A
B
L
E
A
S
T
A
M
P
E
R
L
O
O
P
P
R
O
G
R
A
M
M
A
B
L
E
A
S
K
E
Y
S
W
IT
C
H
L
O
O
P
ZONE 1-8 NOTES
All zones provide Style B supervision
Zone resistance (excluding EOLR):
- Zones 1, 2, 8: 100 ohms max
- Other zones: 300 ohms max
Zone response: 350 - 500mS (all zones)
Connect to 12V, 7AH min/34.4AH max
lead acid batteries using cables supplied.
See instructions for required capacity.
Float charging voltage: 13.7VDC. Battery
normally need not be replaced for
at least 3 yrs.
VISTA-32FB SUMMARY OF CONNECTIONS
J4 KEYPAD PORT #2
See instr. regarding port #2 use
1. GROUND (to keypad black wire)
4. DATA IN 2 (to keypad green wire)
5. AUX PWR #2 (to keypad red wire)
Rating: 10 - 14 VDC,
400mA max. See note 1
7. DATA OUT 2 (to keypad yellow wire)
W6
(BLUE)
INTERFACE TO 5140DLM
MAIN DIALER ON HOOK
VOLTAGE THRESHOLD
INTACT:25V
CUT: 13V
BACK-UP DIALER EARTH
GROUND SCREW
(wire to main PCB
terminal #30)
J2 VOLTAGE TRIGGERS
See instructions for trigger use and programming
(default functions shown)
1. OUT 4 (SILENT PANIC/DURESS)
2. OUT 7 (TROUBLE)
3. OUT 3 (BURGLARY/AUDIBLE PANIC)
4. OUT 6 (SUPERVISORY)
5. OUT 2 (FIRE)
6. OUT 5 (REMOTE KEYPAD SOUNDER)
7. OUT 1 (OPEN/CLOSE)
8. GROUND
9. IN 1 (N.O. LOOP)
RATINGS: OUT 1, 5, 7:
LOW: 2K TO GROUND
HIGH: 10 - 14VDC, 20mA MAX
OTHER OUTS: LOW: 1K TO GROUND
HIGH: 10 - 14VDC THRU 5K
Attach 5140DLM module to main PCB shield using
4 standoffs (supplied)
1 2 3 4 5 6 7 8 9
REFER TO INSTRUCTIONS K3521 FOR ADDITIONAL INFORMATION
WARNING: OWNER'S INSTRUCTION NOTICE NOT TO BE REMOVED
BATTERY TABS
PINS 2, 3, 6, 8 & 9 NOT USED
RJ31X
MAIN
PHONE JACK
BELL OUTPUTS
AUX. RELAY
KEYPAD PORT #1
NOTE 2:
2k EOLR is Ademco model 610-7
CONNECTION OF THE FIRE ALARM
SIGNAL TO A FIRE ALARM HEAD-
QUARTERS OR A CENTRAL STATION
SHALL BE PERMITTED ONLY WITH
THE APPROVAL OF THE LOCAL
AUTHORITY HAVING JURISDICTION.
THE BURGLARY ALARM SIGNAL
SHALL NOT BE CONNECTED TO A
POLICE EMERGENCY NUMBER.
POLLING
LOOP
WARNING:
TO PREVENT
RISK OF
ELECTRICAL
SHOCK,
DISCONNECT
TELCO JACK
BEFORE
SERVICING
THIS PANEL
Connect
RJ31X using
cable supplied.
Supervision is
programmable
TYPES OF FIRE SIGNALLING SERVICE:
Manual fire alarm, automatic fire alarm, sprinkler supervisory and waterflow alarm. UL Listed local control (non-coded).
UL Listed central station and remote station protected premises unit when used with 5140DLM back-up dialer module.
Installation limits under jurisdiction of local authority.
CIRCUIT
(ZONE)
CONTROL UNIT
DELAY-SEC
SMOKE DETECTOR
MODEL DELAY-SEC
THE DELAY TIME MARKED ON THE INSTALLED
DETECTOR(S) IS TO BE USED
Polling Loop Ratings: (supervised)
128mA max. See Note 1.
See instructions for compatible devices
and for max wire run length
BL
BL
BLACK
WHITE
RJ31X
(connect using supplied cable)
Supervision is programmable
EARTH GROUND
Ratings for zones 1,2:
- 10 - 14VDC
- 2mA max for smoke det. (up to 16 detectors
of the type specified in the instructions
can be used)
UL compatibility ID: A
Do not mix fire and burg. sensors on one loop.
N.C. contacts for burg. usage only.
NOTES
TRNSFMR
ALL CIRCUITS ARE POWER LIMITED EXCEPT
THE OUTPUT OF THE POWER TRANSFORMER
TEST BURGLARY SYSTEM WEEKLY
The VISTA-32FB Main Dialer
Complies with FCC Rules, Part 68
FCC Reg. No.: AC398U-68192-AL-E
Ringer Equivalence: 0.7B
The 5140DLM Dialer
Complies with FCC Rules, Part 68
FCC Reg. No.: AC398U-68628-MO-N
Ringer Equivalence: 0.7B
WARNING:
THIS UNIT MAY BE PROGRAMMED TO
INCLUDE AN ALARM VERIFICATION
FEATURE THAT WILL RESULT IN A DELAY
OF THE SYSTEM ALARM SIGNAL FROM
THE INDICATED FIRE CIRCUITS. THE
TOTAL DELAY (CONTROL UNIT PLUS
SMOKE DETECTORS) SHALL NOT EXCEED
60 SECONDS. NO OTHER INITIATING
DEVICES SHALL BE CONNECTED TO
THESE CIRCUITS UNLESS APPROVED BY
THE LOCAL AUTHORITY HAVING
JURISDICTION.
THIS EQUIPMENT
SHOULD BE INSTALLED
IN ACCORDANCE WITH
THE NATIONAL FIRE
PROTECTION ASSOC-
IATION'S STANDARD 72
(NATIONAL FIRE
PROTECTION ASSOC.,
BATTERYMARCH PARK,
QUINCY, MA. 02269).
PRINTED INFORMATION
DESCRIBING PROPER
INSTALLATION,
OPERATION, TESTING,
MAINTENANCE AND
REPAIR SERVICE IS
TO BE PROVIDED WITH
THIS EQUIPMENT.
For commercial fire, bell timeout
must be a minimum of 6 minutes.
NOTE: Use wires that
have insulation rated
for 90
˚
c or higher.
GRN
OUTPUT: 18VAC, 72VA
Not Power Limited
Maintain 1/4" spacing
to other wire
Connect to
Earth Ground
Terminal 30
INPUT:
120VAC, 60HZ,
1.0A max.
Connect to a
dedicated circuit.
Connect to
Proper Earth
Ground. See
instructions.
GRN
Assembled In
Mexico
NOTE: As shipped,
Vista-32FB is suitable
for UL Commercial Fire
Installations. Cabinet
supports up to 14AH
Batteries. Use Vista-ULKT
Cabinet Kit to house
up to 34.4AH Batteries.
Also use this kit along
with 1451 Transformer
for UL Listed Commercial
Burglary Installations.
2A Circuit
Breaker
www.PDF-Zoo.com