– 31 –
Output Programming
The system supports up to 96 outputs. Outputs can be used to perform many different functions and actions. Each output
must be programmed to begin one of four types of ACTIONS at a designated START event, and end that ACTION at a
designated STOP event. The options used to start and stop these devices are described below, followed by the actual
screen prompts and available entries.
The letter(s) in parentheses after each function described below, such as (A) after ACTION, are those that appear in the
various summary displays of programmed data during programming.
ACTION (A)
The "ACTION" of the device is how the device will respond when it is activated by the "START"
programming. You may want the device to activate momentarily, to pulse on and off continuously, or to
remain activated until some other event occurs to stop it. There are five different choices of actions:
•
ACTIVATE for 2 SECONDS and then reset.
•
ACTIVATE and REMAIN ACTIVATED until stopped by some other event.
•
PULSE ON and OFF until stopped by some other event (do not use with an FSA device).
•
NO RESPONSE when the device is not used.
•
TOGGLE on and off alternately with each activation of event.
START (STT)
The "START" programming determines when and under what conditions the device will be activated. The
following START options are available:
1)
EVENT (EV) is the condition (alarm, fault, trouble) that must occur to a zone or group of zones (zone
list) in order to activate the device. These conditions apply
only when a zone list is used. The
different choices for "EVENT" are listed below and in “Output Devices Programming” later in this
section.
ZONE LIST (ZL) is a group of zones to which the “EVENT” applies in order to activate a particular
device. Note that there are a total of 15 zone lists that can be programmed; when the selected
EVENT (alarm, fault or trouble) occurs in any zone in the selected “Start” ZONE LIST (01-15),
activation of the selected device will START.
2)
ZONE # A specific zone going into alarm, fault, trouble, or restore (Event programming) can be used to
start the Output action. Enter the 3-digit zone number (000-032).
3)
ZONE TYPE/SYSTEM OPERATION (ZT). If all zones to be used to start the device have the same
response type, and there are no other zones of this type which are not to activate this device, then
“ZONE TYPE” may be used instead of using a "ZONE LIST" and "EVENT” to activate the device.
If a System Operation, such as “DISARMING” or “ANY FIRE ALARM” is to activate the device, the
appropriate choice would also be entered under the “ZONE TYPE” option.
The “ZONE TYPE/SYSTEM OPERATION” option functions independently of the “EVENT/ZONE
LIST” combination.
If a specific "ZONE TYPE" is chosen, any zone of that response type going into alarm, trouble, or fault
will cause the device to activate as selected in "ACTION.” If the same “ZONE TYPE” is also chosen
for the STOP programming, any zone of that type that
restores will de-activate the device.
If a "SYSTEM OPERATION" is chosen, that operation will cause the device to activate as selected in
"ACTION.” The different choices for "ZONE TYPE" and "SYSTEM OPERATION" are listed in “Output
Devices Programming” later in this section, and on the Programming Form.
4)
PARTITION No. (P). The device's "Start" ZONE TYPE/SYSTEM OPERATION may be limited to an
occurrence on one partition (1-2), or any partition (0).
STOP (STP):
The "STOP" programming determines when and under what conditions the device will be de-activated.
The following options are available:
1). RESTORE ZONE LIST (ZL). If a "ZONE LIST" is used as the “Stop” event, the device will de-activate
when all the zones in that list restore from a previous fault, trouble, or alarm condition. This will occur
regardless of what is programmed to "START" the device; therefore, a "RESTORE ZONE LIST" would
normally only be used when a "ZONE LIST" is used to start the device.
2). ZONE TYPE/SYSTEM OPERATION (ZT). Instead of using a "RESTORE ZONE LIST," a specific
zone (response) type or system operation action can be selected to de-activate the device.
If a specific "ZONE TYPE" is chosen, any zone of that response type that restores from a previous
alarm, trouble, or fault condition will cause the device to de-activate.
If a "SYSTEM OPERATION" is chosen, that operation will cause the device to de-activate. The
different choices for "ZONE TYPE" and "SYSTEM OPERATION" are listed in “Output Devices
Programming” later in this section, and in the Programming Form.
The “ZONE TYPE/SYSTEM
OPERATION” option functions independently of the “[RESTORE]ZONE LIST” option.
3)
PARTITION No. (P). The device's "Stop" Zone Type/System Operation may be limited to an
occurrence on one partition (1-2), or on any partition (0).
www.PDF-Zoo.com