background image

10

Summary of Main PCB Connections

Battery / Ground Terminals

GND

Equipment Ground Terminal - connection must be intact at all times.

BATT-

Battery Negative - Connect to the -ve (black) terminal of the battery.

BATT+

Battery Positive - Connect to the +ve (red) terminal of the battery.

Output Triggers (Terminal PLA)

1.

Fire trigger

2.

Panic trigger

3.

Alarm (Intruder) trigger

4.

Tamper trigger - responds to tamper alarms when the system is unset.
When full set, a tamper alarm activates the Alarm output trigger.

5.

Fault trigger - responds to low battery, mains fail, memory checksum
failure and watchdog reset.

6.

Programme trigger - activates when programming mode is entered.

Power / Keypad Terminals (Terminal PLB)

AC

These two terminals connect to the 13 V a.c. output of the mains
transformer. They are not for direct connection to the mains supply.

Data Out Connects to the Data Out (yellow) terminal of each fixed LCD

keypad on the system.

Data In

Connects to the Data In (green) terminal of each fixed LCD keypad.

12 AUX

Auxiliary 12 V supply - two pairs of terminals are available for
connection of remote keypads and auxiliary fused devices.

Bell / Zone / SW- terminals

1.

Switched Negative Supply - This output can be programmed as:
(a) Negative supply for smoke detectors or other latching devices
which require the interruption of the supply to reset. The output is
normally 0 V switching to +12 V for 6 seconds on the second entry
of Code + Off after an alarm condition. The output can also be
activated at any point in the unset state by pressing the 

Ö

 and 1 keys

together.
(b) Printer data output for a serial printer.
(c) Sounder output.

2.

Strobe negative - for connection with external strobe negative.

3.

Positive bell / strobe supply - common positive, limited by fuse to 1
Amp maximum (labelled F3 in Figure 2.1 PCB Connections).

4.

External bell negative - for connection with switched negative trigger
on external bell or SAB switched negative trigger.

5 - 36

Alarm zones 1-8, wired as standard double poll zones. Normally
open devices may be connected between alarm and tamper loops.
Zones programmed as Not Used must have the both alarm and tamper
loops linked out.

www.PDF-Zoo.com

firealarmresources.com

Summary of Contents for VISTA 10

Page 1: ...1 VIST VIST VIST VIST VISTA 10 UK A 10 UK A 10 UK A 10 UK A 10 UK ENGINEER S ENGINEER S ENGINEER S ENGINEER S ENGINEER S MANU MANU MANU MANU MANUAL AL AL AL AL www PDF Zoo com firealarmresources com...

Page 2: ...2 www PDF Zoo com firealarmresources com...

Page 3: ...Main PCB Connections 10 COMMUNICATION 12 General Information 12 Installation 12 Telephone Line Wiring 13 REN 14 Warning 14 Approval 14 Completion of Installation 14 SECTION 3 PROGRAMMING THE VISTA 10...

Page 4: ...VICE NOTES 23 1 Reset 23 2 Bypassing Isolating Zones 23 3 User Codes 23 4 View Event Log 23 5 Set Real Time Clock 23 6 Communication Test 23 7 Troubleshooting 24 ADEMCO LIMITED WARRANTY 25 www PDF Zoo...

Page 5: ...in a position where it may be subject to dripping of or splashing with water or other fluids Fixing The control must be securely fixed to a vertical smooth solid surface which is part of the fabric o...

Page 6: ...ust only be removed if cables are to enter the cabinet at that point The hole must be covered by the trunking or conduit or by means of a blanking grommet It must not be possible to push a finger or s...

Page 7: ...cross sectional area of 0 75mm and the insulating material on each conductor must be a minimum of 0 4mm thick polyvinyl chloride PVC Flexible cables must conform to the requirements of IEC Publicatio...

Page 8: ...Transformer Mains fuse Knock out top Saftey Statement Terminals marked Excessive Voltage are for connection for 240V AC 50Hz mains supply only Terminals marked SELV Safety Extra Low Voltage are for c...

Page 9: ...ter 1 2 3 4 AWAY to arm control After 30 seconds the system will set Enter 1 2 3 4 OFF to disarm the system This confirms control and keypad are operating correctly 6 Remove a c power before opening t...

Page 10: ...keypad 12 AUX Auxiliary 12 V supply two pairs of terminals are available for connection of remote keypads and auxiliary fused devices Bell Zone SW terminals 1 Switched Negative Supply This output can...

Page 11: ...OUT DATA IN YELLOW GREEN RED BLACK VE RTN ZONE 9 Bell Tamper T A ZONE 8 T A ZONE 7 T A ZONE 6 T A ZONE 5 T A ZONE 4 T A ZONE 3 T A ZONE 2 T A ZONE 1 Switch ve 12V Bell ve Strobe ve A B BC Telephone l...

Page 12: ...each zone The chan nels are pre assigned as type 3 and only require changing if a different report or no reporting of a zone is required Besides reporting an alarm a restore report may also be sent fo...

Page 13: ...dial and multi frequency DTMF signals This unit has been approved for the use of the following facilities Modem Loop disconnect signalling Multi frequency signalling Auto calling Auto answering Any o...

Page 14: ...nanymaterialwaynotauthorisedbyBABT or it is used with or connected to Internal software that has not been formerly accepted by BABT External control software or external control apparatus which causes...

Page 15: ...15 Figure 2 2 Telephone Line Connections www PDF Zoo com firealarmresources com...

Page 16: ...16 www PDF Zoo com firealarmresources com...

Page 17: ...odified using the key or viewed using the key To programme a field Enter field number field entry in engineer mode e g to change the engineer code to 1111 enter 00 then 1111 where 00 is the field numb...

Page 18: ...ermi nate connected between Data In and Data Out on keypad bus Output Options 12 Bell Delay 0 Instant Bells 1 10 minute bell delay 13 Bell Duration Multiples of 2 Minutes i e 01 2 mins 10 20 mins 14 S...

Page 19: ...Engineer 2 Technistore Reset Zone Programming Options 02 Zone 1 8 Response 05 Zone 99 Panic Assign zone type e g 06 or 07 39 Zone 1 8 Forced Walk Test 0 0 4 1 1 0 0 0 0 1 0 3 0 3 0 3 0 3 0 4 0 3 0 3...

Page 20: ...gicom Format 0 Ademco Contact ID 1 High Speed 8 channel 49 Checksum Verification 0 No 1 Yes only used on ADEMCO receivers Before entering new numbers type 33 primary or 34 secondary to delete previous...

Page 21: ...68 Non alarm reports a Open b Close c Low Battery d Not Used e 24 HourTest f Watchdog Reset g Cancel Code Abort h Program Mode Access 61 Digicom Channel Codes Zones 1 8 62 Digicom Channel Code Zones 9...

Page 22: ...mpleted 35 Downloader Tel No 36 Downloader ID 37 Downloader Command Enables a Dialler Shut Down b System Shut Down c Access When Set d Remote Bypass Isolate e Remote Disarm f Remote Arm g Upload Progr...

Page 23: ...code 2 confirmation beeps follows acceptance of new code 4 View Event Log The full real time event log may be uploaded to the Download computer or printed out from the control via an interface and se...

Page 24: ...u have lost mains power BAT Battery is running low OC indicates control is not communicating with the panel CE Call Engineer CD Fault with the Telco line or see field 22 CF Comms failure to the C S CS...

Page 25: ...R INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY EXPRESS OR IMPLIED OR UPON ANY OTHER BASIS OF LI ABILITY WHATSOEVER EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE SELLER S OWN NEGLIGENCE OR...

Page 26: ...26 www PDF Zoo com firealarmresources com...

Page 27: ...27 www PDF Zoo com firealarmresources com...

Page 28: ...28 IE1 4110 ISSUE A 30 7 99 www PDF Zoo com firealarmresources com...

Reviews: