Note:  
1  Do  not  leave  the  jumper  in  position  5  (Size  1,  3)  or  position  6  (Size  2)  or  Battery  Start  (Size  4); 

otherwise, 

in  Backup  mode,  the 

battery  discharges 

completely 

close 

to 

Zero.  

For  Size  2:  must  be  require  CBI2410A/S  or  CBI485A/S  (/S  means  start  with  battery  functions, 
otherwise only start with Input Mains) 

2  CBI2420A, CBI1235A, CBI4810A, CBI245ASDXX Replaces the fast charge in UPS disabling: 

o

 Closed  contact:  back-up  (UPS)  enabled.  System  shut  down  after  xx  min  (depends  on  time 

minutes required in SD version).   

o

 Contact open: Inhibit backup function. No UPS enabled.   

3  Jumper  present  in  Fast  Charge  means  also  that  every  288h,  the  device  goes  in  “Cycling  Refresh 

Charging”.  This  mode  continues  for  85  minutes  at  the  same  voltage  condition:  2.4V/Cell;  for  Lead 
Acid Batteries. 

4  Please note that it is possible to use lithium-charging curve just with a single BMS Battery. From the 

release: 

Size1

:12Vdc  Output:  S13  R6;  24Vdc  Output:  S13  R7 

Size2

:  24Vdc  Output:  S92  R3 

Size3

:12Vdc, 24Vdc, 48Vdc Output: S40 R13 

Size4

: S130 R5 

5  Whit this selection it is possible to change the parameters of the chemistry selected.  

a.  First, you have to select the battery chemistry  
b.  Select “Config Mode”. 
c.  Change  the  parameters  with  DPY351  or  ADELVIEWSsystem.  After  update,  it  is  possible 

disconnect the programmer and use the device as standalone device. 

d.  If you remove the “Config Mode” all parameter come back to default chemistry selection 

9.4  DIAGNOSTIC AND CONTROLS  

All CBI devices support the user during installation and operation. A Blink code of Diagnosis Led allows to 
discriminate among various possible faults. 
Error conditions, “LED Battery Fault” ON and “LED Diagnosis” blinking with sequence; see Display Signal 
section. 

  Check  for  accidental  disconnection  of  the  battery  cables  and  immediately  switched  off  the  output 

power. 

  Battery not connected: If the battery is not connected no output on the Load side. 

  Test of quality wire connections: During Float charge the quality (resistance) on the battery connection 

is checked every 60 sec. This to detect if the cable connection has been properly made. 

  Battery  in  Open  Circuit  or  Sulphated:  In  Float  charging  mode,  the  All  In  One  performs  internal 

impedance test every 220 minutes. 

  Reverse  Polarity  check:  If  the  battery  it  is  connected  with  inverted  polarity,  the  All  In  One  is 

automatically protected. 

  Test of battery voltage connections: Appropriate voltage check, to prevent connection of wrong battery 

types, more or less than the nominal voltage. 

  End of Charge check : When the battery is completely fully charged, the device automatically switch in 

Float charging mode. 

  Check for Battery Cells in short circuit: Thanks to specific algorithms of evaluation, the CBs recognize 

batteries with cells in internal short circuit. In Float charge every 220 minutes test of element in short 
circuit. 

9.5  PROTECTION FEATURES 

 

On the primary side:

 the device is equipped whit an internally fuse. If the internal fuse is activated, it 

is  most  probable  that  there  is  a  fault  in  the  device.  If  happen,  the  device  must  be  checked  in  the 
factory. 

 

On the secondary side Battery and load:

 The device is electrically protected against short circuits 

and overload. 

 

Polarity Inversion:

 the module it is automatically protected against inversion of battery polarity and 

connection of load inverted. 

 

Over current and output short circuit: 

 the unit limits the output current (see the technical data). 

 

Deep  discharge: 

not  possible.  The  unit  disconnects  the  battery  when  a  minimum  voltage  level  is 

reached.

  

9.6  CHARGING CURVE 

Automatic  multi-stage  operation  and  real  time  diagnostic  allows  fast  recharge  and  recovery  of  deep 
discharged  batteries,  adding  value  and  reliability  to  the  system  hosting  the  CBI  device.  The  type  of 
charging  is  Voltages  stabilized  and  Current  stabilized  IUoU.  Five  charging  phases  are  identified  by  a 
flashing code on a Diagnosis LED. To maintain the Output Load in lower Voltage state, don’t put jumper 
in position 6, in this case no boost charge but only Float charge. Fast/Bulk Charge means also that every 
288h, the device goes in “Cycling Refresh Charging” for 85 minutes at 2.4V/Cell. 

Summary of Contents for ALL IN ONE CBI Series

Page 1: ...y efficiency reduces risk of battery damage and allows a safe operation in permanent connection Predefined curves can be selected by jumpers or DIP switch to optimize the charge of different battery t...

Page 2: ...or Load DC Bus one Input Output for connection to the battery N 1 battery 12 Vdc for CBI 12xx N 2 battery 12 Vdc connected in Series for CBI 24xx N 4 battery 12 Vdc connected in Series for CBI 48xx 5...

Page 3: ...installation clearance of 10 mm left right between two power supplies and avoid installing the power supplies on top of each other Note Avoid return voltage e g from a decelerating motor or battery w...

Page 4: ...45 min 20 h Load 12 A No 3 min 12 min 30 min 600 min Load 15 A No No 9 min 20 min 400 min Load 20 A No No 7 min 13 min 240 min 6 LAY OUT AND CONNECTIONS 7 INPUT AND OUTPUT LOAD AND BATTERY CONNECTION...

Page 5: ...wer 2 See Diagnosis Led 8 1 4 Relay Contact Rating Max DC1 30 Vdc 1 A AC1 60 Vac 1A Resistive load EN 60947 4 1 Min 1mA at 5 Vdc Min permissive load 8 1 5 Charging Mode STATUS Status Led Diagnosis No...

Page 6: ...Acid Gel Ni Cd option They guarantee battery reliability in time by continuously testing the internal impedance status avoids any possible risk of damages and grants a permanent reliable and safe conn...

Page 7: ...er Position Size 1 Jumper Position Size 2 Jumper Position Size 3 Dip Switch Position Size 4 Float charge Volt Cell Fast charge Volt Cell Open Lead 2 23 2 40 AGM Low 2 25 2 40 Gel Battery 2 30 2 40 NiC...

Page 8: ...he quality resistance on the battery connection is checked every 60 sec This to detect if the cable connection has been properly made Battery in Open Circuit or Sulphated In Float charging mode the Al...

Page 9: ...STICS The unit is a SLAVE in a MODBUS network The slave units are compliant to the following specifications Transmission mode MODBUS RTU Electrical Interface RS485 half duplex serial line Baud rate 48...

Page 10: ...onnection Diagram Size3 CBI500 DPYCONN500 is a special cable for the connection of CBI Size3 and the other device max leght 0 5m RJ45COUPLER is e T connection RJ45 for daisy Chain with CBI Size3 RJCON...

Page 11: ...ections to the external device like RTU PC DPY351 For the connection to RTU PLC or similar devices refer to the instruction manuals Modbus specifications_R14 Web Site www adelsystem com For configurat...

Page 12: ...ity to EN60950 UL60950 1 and CSA C22 2 No 60950 1 07 Information Technology Equipment Safety Part1 General Requirement Device is intended to be installed in a cabinet protected from external shocks or...

Reviews: