9.7  THERMAL BEHAVIOUR 

Surrounding  air  temperature  50°C.  For  ambient  temperature  of  over  50°C,  the  output  current  must  be 
reduced by 2.5% per °C. Max 70°C At the temperature of 70°C the output current will be 50% of In. The 
equipment  does  not  switch  off  in  case  of  ambient  temperature  above  70°C  or  thermal  overload.  The 
devices are protected for Over temperature conditions “worst case”; in this situation the device Shut-down 
the output and automatic restart when temperature inside fall. 

10   MODBUS 

Some devices are provided of Modbus “RTU” communication protocol port; which requires the only one 
device be the Master, all the others must be slave. 
Hardware interface: RS485.  

10.1  ELECTRICAL CHARACTERISTICS 

The unit is a 

SLAVE

 in a MODBUS network. The slave units are  compliant to the following specifications: 

Transmission mode:  

MODBUS RTU 

Electrical Interface: 

RS485 half-duplex serial line 

Baud rate: 

4800 / 9600 / 19200 / 38400 (default) bps 

Data format: 

8 data bits 

Parity:  

even (default) / odd / none 

Stop bits: 

1 (parity odd or even) / 1 or 2 selectable (parity none) 

Slave address: 

configurable in the range 1 (default) to 247 

Connector type: 

RJ45 

Cable: 

Shielded twisted pair, 8-wire RJ-45 plug 

 

 

 

 

Size 3 

Size4 

Connector name 

AUX2 

AUX3 

Pinout (fig. below) 

A = pin 2, B = pin 1,  
Common = pin 3 

A = pin 5, B = pin 4, 
Common = pin 3 

10.2  HOW TO CONNECT MODBUS 

10.2.1 Daisy Chain general connection Diagram 

To connect the device in ModBus field, please use AUX2 and AUX3 Port. 

  Port: AUX 2 No. 13 is Present only in Sizes 3 and Sizes 4, MODBUS connection via RJ45 connector. 

  Port: AUX 3 No. 14 Present only in Sizes 4. The function is the same of Auxiliary Output “AUX 2” 

Summary of Contents for ALL IN ONE CBI Series

Page 1: ...y efficiency reduces risk of battery damage and allows a safe operation in permanent connection Predefined curves can be selected by jumpers or DIP switch to optimize the charge of different battery t...

Page 2: ...or Load DC Bus one Input Output for connection to the battery N 1 battery 12 Vdc for CBI 12xx N 2 battery 12 Vdc connected in Series for CBI 24xx N 4 battery 12 Vdc connected in Series for CBI 48xx 5...

Page 3: ...installation clearance of 10 mm left right between two power supplies and avoid installing the power supplies on top of each other Note Avoid return voltage e g from a decelerating motor or battery w...

Page 4: ...45 min 20 h Load 12 A No 3 min 12 min 30 min 600 min Load 15 A No No 9 min 20 min 400 min Load 20 A No No 7 min 13 min 240 min 6 LAY OUT AND CONNECTIONS 7 INPUT AND OUTPUT LOAD AND BATTERY CONNECTION...

Page 5: ...wer 2 See Diagnosis Led 8 1 4 Relay Contact Rating Max DC1 30 Vdc 1 A AC1 60 Vac 1A Resistive load EN 60947 4 1 Min 1mA at 5 Vdc Min permissive load 8 1 5 Charging Mode STATUS Status Led Diagnosis No...

Page 6: ...Acid Gel Ni Cd option They guarantee battery reliability in time by continuously testing the internal impedance status avoids any possible risk of damages and grants a permanent reliable and safe conn...

Page 7: ...er Position Size 1 Jumper Position Size 2 Jumper Position Size 3 Dip Switch Position Size 4 Float charge Volt Cell Fast charge Volt Cell Open Lead 2 23 2 40 AGM Low 2 25 2 40 Gel Battery 2 30 2 40 NiC...

Page 8: ...he quality resistance on the battery connection is checked every 60 sec This to detect if the cable connection has been properly made Battery in Open Circuit or Sulphated In Float charging mode the Al...

Page 9: ...STICS The unit is a SLAVE in a MODBUS network The slave units are compliant to the following specifications Transmission mode MODBUS RTU Electrical Interface RS485 half duplex serial line Baud rate 48...

Page 10: ...onnection Diagram Size3 CBI500 DPYCONN500 is a special cable for the connection of CBI Size3 and the other device max leght 0 5m RJ45COUPLER is e T connection RJ45 for daisy Chain with CBI Size3 RJCON...

Page 11: ...ections to the external device like RTU PC DPY351 For the connection to RTU PLC or similar devices refer to the instruction manuals Modbus specifications_R14 Web Site www adelsystem com For configurat...

Page 12: ...ity to EN60950 UL60950 1 and CSA C22 2 No 60950 1 07 Information Technology Equipment Safety Part1 General Requirement Device is intended to be installed in a cabinet protected from external shocks or...

Reviews: