g. Water pockets in the supply line, caused by low points, will provide wet steam to the coil possibly
causing steam coil damage.
ALL
horizontal runs of steam supply piping
should be
pitched 1/4-inch
for every one (1) foot back towards the steam supply header causing the condensate in the line to
drain to the header. Install a bypass trap in any low point to eliminate wet steam.
IMPORTANT
: Flexible hose/coupling
must be
used. Coil Failure due to hard plumbing
connections will
VOID THE WARRANTY.