Appendix A: CABLE LOSS
The cable resistance R (ohms) for 1 conductor is calculated with following formula:
•
R (ohms) = resistivity of material (ohm m) × length (m)/cross sectional area (m
2
)
•
For copper conductors the resistivity is 1.72 10-8 (m
2
)
Example; for 1 km 2.5 mm
2
copper conductor, the resistance R is calculated as follows:
1.72 10-8 × 1000 / 2.5 10-6 m
2
= 6.88 ohms
The loss (Watt) is then R × I
2
or 6.88 ohms × 6.6
2
A
2
= 299.69 W/km or 0.299 W/m.
The loss (Watt) for a secondary cable with 2 conductors is thus 2 × 0.299 = 0.599 or 0.6 W/m.
As such we can calculate:
•
Secondary cable for a 2.5 mm
2
Cu-wire (2 conductors): 0.6 W/m
•
Secondary cable for a 4 mm
2
Cu-wire (2 conductors): 0.4 W/m
•
Primary cable for a 6 mm
2
Cu-wire (1 conductor): 0.12 W/m
The cable between the isolation transformer and the lamp adds losses that cannot be ignored when dimensioning the circuits
and selecting rating for secondary transformers and regulators.
WARNING
Cable lengths should not exceed 100 meters.
For a secondary cable of e.g., 20 m of 2.5 mm
2
CU-wire, 20 m × 0.6 W/m = 12 W equals the additional loss to be taken into
account.
For a primary cable of e.g., 100 m of 6 mm
2
CU-wire, 100 m × 0.12 W/m = 12 W equals the additional loss to be taken into
account.
UM-5073, Rev. 1.0, 2021/07/13
51
Copyright
©
ADB SAFEGATE, All Rights Reserved
Summary of Contents for RELIANCE Omni 1-Dome
Page 1: ...RELIANCE Omni 1 Dome 8 inch User Manual UM 5073 Rev 1 0 2021 07 13 ...
Page 2: ......
Page 8: ...RELIANCE Omni 1 Dome List of Figures viii Copyright ADB SAFEGATE All Rights Reserved ...
Page 10: ...RELIANCE Omni 1 Dome List of Tables x Copyright ADB SAFEGATE All Rights Reserved ...
Page 20: ...RELIANCE Omni 1 Dome General Information 10 Copyright ADB SAFEGATE All Rights Reserved ...
Page 26: ...RELIANCE Omni 1 Dome Installation 16 Copyright ADB SAFEGATE All Rights Reserved ...
Page 28: ...RELIANCE Omni 1 Dome Operation 18 Copyright ADB SAFEGATE All Rights Reserved ...
Page 52: ...RELIANCE Omni 1 Dome Maintenance 42 Copyright ADB SAFEGATE All Rights Reserved ...
Page 54: ...RELIANCE Omni 1 Dome Troubleshooting 44 Copyright ADB SAFEGATE All Rights Reserved ...
Page 60: ...RELIANCE Omni 1 Dome POWER TABLE 50 Copyright ADB SAFEGATE All Rights Reserved ...
Page 62: ...RELIANCE Omni 1 Dome CABLE LOSS 52 Copyright ADB SAFEGATE All Rights Reserved ...
Page 66: ......