![ADB Safegate CRE 10 Installation Manual Download Page 58](http://html1.mh-extra.com/html/adb-safegate/cre-10/cre-10_installation-manual_2847401058.webp)
58
A.07.370e - Edition 2.0
Installation
6.12 Connect output to series circuit
The procedures show how to connect the integrated output connections:
- With SCB (option). See § 6.12.1.
- With SCO (option). See § 6.12.2.
- With CS (option). See § 6.12.3.
If the output connection is not integrated in the equipment, see the dedicated installation manuals:
- AGLAS Master;
- External SCO.
6.12.1 Connect output to series circuit with SCB
Strip cables
1. Strip the series circuit cables at the end.
- A: unscreened cables
- X: 16 mm
-
∅
Y: less than or equal to 18 mm
- B: screened cables
- X: 16 mm
-
∅
Y: less than or equal to 18 mm
- U: 11 mm
- Z: 77 mm
Remove the box panel
1. Loosen the screws (A).
2. Remove the box panel (B).
CAUTION
If the series circuit cable is screened, connect the screen to an earthing network either
inside or outside the equipment.
X
Z
U
X
Y
A
B
Y
A
A
B
Summary of Contents for CRE 10
Page 1: ...A 07 370e Edition 2 0 Installation Manual Constant Current Regulator Type CRE ...
Page 14: ...14 A 07 370e Edition 2 0 Safety ...
Page 44: ...44 A 07 370e Edition 2 0 Inspection and transport ...
Page 64: ...64 A 07 370e Edition 2 0 Installation ...
Page 85: ...A 07 370e Edition 2 0 85 Technical data ...
Page 86: ...adbsafegate com ...