20
Installer's Handbook (Evo) - 660Y3000 • A
EN
Boiler Settings
Boiler Settings
Model HeatMaster
Lockout Temp.
221°F [105°C]
Modbus Address
0=BCST
Pump settings
Ignition Level
3750rpm
Mix zone high limit
45°C
The
Pump Settings
menu allows to choose the right pump configuration to the chosen hydraulic configuration.
The
Current Pump Config
indicates which configuration is currently selected for the appliance.
Two appliance configuration modes are available : a preset configuration mode and a flexible configuration mode.
Touch the
UP
or
DOWN
soft keys to scroll through the options, then
OK
to validate your selection.
In the
Preset Pump Config.
(preferred selection) you can choose from a number of preset pump configu-
rations. Only the configurations usable with a certain model/type of appliance will appear in the list. The
configurations are detailed in
. Each configuration is detailed through one or
several hydraulic diagrams, a table indicating the electrical connections and a list of the parameters to be
defined in ACVMax.
Touch the
UP
or
DOWN
soft keys to scroll through the settings, then
OK
to validate your selection.
The
Flexible Pump Config.
menu allows to customize the connection of the pump(s) installed in the primary
circuit in the chosen hydraulic configuration. Only select this option when the preset configurations do not
offer you a solution. In this menu you have to choose, per relay, for which heat demand / function it will be ac-
tivated. The relays are allocated as follows by default (see picture below for physical location on the optional
terminal blocks) :
Flex. Relay 1 → CH (int. pump)
Flex. Relay 2 → DHW (pump)
Flex. Relay 3 → P3 (pump)
Flex. Relay 4 → ERR (error)
Flex. Relay 5 → FL (Flame)
Flex. Relay 6 → P4 (pump)
Touch the
UP
or
DOWN
soft keys
to scroll through the settings, then
OK
to validate your selection.
Pump Settings
Current Pump Config
Config 16
Preset Pump Config
Flexible Pump Config
Pump PWM minimum
100%
Pump Settings
Current Pump Config
Config 16
Preset Pump Config
Flexible Pump Config
Pump PWM minimum
100%
Pump Settings
Current Pump Config
Config 16
Preset Pump Config
Flexible Pump Config
Pump PWM minimum
100%
Flexible Pump Config
Flex. Relay 1 (CH)
Flex. Relay 2 (DHW)
Flex. Relay 3 (P3)
Flex. Relay 4 (ERR)
Flex. Relay 5 (Flame)
Flex. Relay 6 (P4)
Preset Pump Config
Config 1
Config 2
Config 3
Config 4
Config 5
Config 6
X12
P14
1
2
X10
1
2
3
4
B
B
W
Br
B
B
B
Or
1 2 3 4 5 6 7 8
8
7
6
5
4
3
2
1
1
2
3
4
5
6
X100
6
Y/Gr
W
B
Y/Gr
Br
B
Y/Gr
B
Or
W
V
230 V
Br
B
V
W
B
Br
B
B
9 10 11 12 13 14 15 16
X100
7
Y/Gr
Y/Gr
16
15
14
13
12
11
10
9
B
Br
Y/Gr
B
Br
B
Br
Y/Gr
230 V
Flame
DHW
P3
P4
Error
P4
P3
FL
DESCRIPTION AND OPERATION
Summary of Contents for ACVMax Touch
Page 48: ......