12
Installer's Handbook (Evo) - 660Y3000 • A
EN
CH Settings
Heating Settings
CH1 Min. Setpoint
27°C
Outdoor Curve Coldest Day
-12°C
Outdoor Curve Warmest Day
18°C
CH2 Circuit
Enabled
CH2 Max. Setpoint
60°C
CH2 Min. Setpoint
27°C
CH2 Min.
Setpoint
27°C
15°C
88°C
CH2 Min. Setpoint
is the minimum setpoint for a CH2 heating call when an Outdoor Curve option is chosen in Demand Type. This
setting is not applicable when a Setpoint option is chosen in Demand Type.
Touch the
LEFT
or
RIGHT
soft keys to adjust the CH2 Minimum Setpoint then touch the
OK
key to store the setting.
Default: 27°C
Warm Weather Shutdown
allows to enter an optional outdoor temperature at which to disable the central heating function. The Appli-
ance will continue to respond to a domestic hot water call or a 0- 10V Modulation Signal when the outdoor temperature exceeds the
Warm Weather Shutdown Temperature setting.
Touch the
LEFT
or
RIGHT
soft keys to adjust the Warm Weather Shutdown Temperature then touch the
OK
key to store the setting and
complete the Heating setting.
The Warm Weather Shutdown icon ( ) is displayed on the home screen when the outdoor temperature reaches the Warm Weather
Shutdown Temperature.
Default: OFF
.
Heating Settings
Outdoor Curve Coldest Day
-12°C
Outdoor Curve Warmest Day
18°C
CH2 Circuit
Enabled
CH2 Max. Setpoint
60°C
CH2 Min. Setpoint
27°C
Warm Weather Shutdown
Off
Warm Weather Shutdown
Off
Off
25°C
CH2 Circuit
allows the CH2 heating call to be enabled and disabled.
Touch the
UP
or
DOWN
soft keys to select Enabled or Disabled then touch the
OK
key to store the setting.
Enabled
– The appliance will respond to a CH2 heating call
Disabled
– The appliance will not respond to a CH2 heating call
Default: Enabled
CH2 Max. Setpoint
is the maximum setpoint for a CH2 heating call when an Outdoor Curve option is chosen in Demand Type.
CH2 Maximum Setpoint is the fixed setpoint for a CH2 heating call when a Setpoint option is chosen in Demand Type.
Touch the
LEFT
or
RIGHT
soft keys to adjust the CH2 Maximum Setpoint then touch the
OK
key to store the setting.
Default: 60°C
Heating Settings
Abs. Max CH Setpoint
87°C
CH1 Max. Setpoint
82°C
CH1 Min. Setpoint
27°C
Outdoor Curve Coldest Day
-12°C
Outdoor Curve Warmest Day
18°C
CH2 Circuit
Enabled
CH2 Circuit
Disabled
Enabled
Heating Settings
CH1 Max. Setpoint
82°C
CH1 Min. Setpoint
27°C
Outdoor Curve Coldest Day
-12°C
Outdoor Curve Warmest Day
18°C
CH2 Circuit
Enabled
CH2 Max. Setpoint
60°C
CH2 Max.
Setpoint
60°C
20°C
90°C
DESCRIPTION AND OPERATION