Installer's Handbook (Evo) - 660Y3000 • A
EN
CH Settings
CH Post Pump Time
sets how long the central heating circulators will continue to operate at the completion of a heating call.
Any call during the CH Post Pump Time will be ignored until the post pump has completed. The CH Post Pump Time feature
allows the heat remaining in the appliance at the completion of a call to be sent to the heating system, which will improve the
overall efficiency of the system.
Touch the
LEFT
or
RIGHT
soft keys to adjust the CH Post Pump Time then touch the
OK
key to store the setting.
Default: 5 min
Circulation Pump Permanent
allows the central heating circulators to be constantly enabled even without a central heating call.
A domestic hot water call will cause the circulators to be disabled during the domestic call as long as DHW Priority is enabled.
Touch the
UP
or
DOWN
soft keys to select Enabled or Disabled then touch the OK key to store the setting.
• Enabled
– The central heating circulators will be enabled for constant circulation without a central heating call.
• Disabled
– The central heating circulators will only be enabled during a central heating call.
Default: Disabled
Heating Settings
Outdoor Curve Warmest Day
18°C
CH2 Circuit
Enabled
CH2 Max. Setpoint
60°C
CH2 Min. Setpoint
27°C
Warm Weather Shutdown
Off
Circulation Pump Perman.
Disabled
Circulation Pump
Permanent
Disabled
Enabled
Heating Settings
CH2 Circuit
Enabled
CH2 Max. Setpoint
60°C
CH2 Min. Setpoint
27°C
Warm Weather Shutdown
Off
Circulation Pump Perman.
Disabled
CH Post Pump Time
5 min
CH Post
Pump Time
5 min
Off
20 min
Heating Settings
CH2 Max. Setpoint
60°C
CH2 Min. Setpoint
27°C
Warm Weather Shutdown
Off
Circulation Pump Perman.
Disabled
CH Post Pump Time
5 min
Freeze Protection
Enabled
Freeze Protection
Enabled
Disabled
The
Freeze Protection
menu allows the feature to be enabled and disabled. The built-in frost protection mechanism activates the sys-
tem pumps as soon as the flow temperature [NTC1 probe] drops below 7°C. As soon as the flow temperature is at 5°C, the burner starts
up until the flow temperature rises above 15°C. The pumps continue to run for around 10 minutes.
Touch the
UP
or
DOWN
soft keys to select Enabled or Disabled then touch the
OK
key to store the setting.
•
Enabled
– The Frost Protection feature protects the installation from freezing at a predetermined system flow temperature.
•
Disabled
– The Frost Protection feature is disabled. Only the pumps operate.
Default: Enabled
Frost Protection Setpoint
allows to define the outside air temperature at which the anti-freeze function is activated (only available if
an outdoor temperature sensor is connected). The pumps are activated when the outside temperature drops below the threshold
defined in this menu.
Touch the
LEFT
or
RIGHT
soft keys to adjust the Freeze temperature Setpoint then touch the
OK
key to store the setting.
In order to enable the protection of the whole system against freezing, all the valves of the radiators and the convectors should be
completely open.
Default: -30°C
Heating Settings
CH2 Min. Setpoint
27°C
Warm Weather Shutdown
Off
Circulation Pump Perman.
Disabled
CH Post Pump Time
5 min
Freeze Protection
Enabled
Frost Protection Setpoint
-30°C
Frost Protection
Setpoint
-30°C
-30°C
10°C
DESCRIPTION AND OPERATION