Zone Control / Remote Sensor Installation
Location
•
ENSURE that the zone device (zone controller or remote sensor) distance
from wall controller (master or secondary) is within the recommended RF
range of 30m.
•
Do not install the zone devices on external walls, directly below the supply
air grille or near other additional heat load sources, as these locations may
alter sensor readings.
•
Do not install zone devices near magnetic, metallic objects or install near
power cables as these may effect the RF data signal it sends and receive
wall controller.
•
Avoid looping excess cable.
•
Ensure there is an ample space (100mm) around the zone device to ensure
proper air temperature reading and access for removal.
•
It is required to use the provided wall anchors and screws to secure the
device on the wall.
•
If a zone device is required to be replaced, remember to unpair the existing
controller and pair the new one to the master controller.
•
Use a maximum of 20m RJ45 cable.
•
Plug the power cable to its designated zone damper terminal or zone
module terminal (using 3-way cable joiner).
•
DO NOT use battery and zone power cable at the same time.