8
A5LCY_(i)
Application Information
Refrigerant Piping
Piping Length and Elevation
If the pipe is too long, both the capacity and reliability of the unit will drop. As the number of bends increases,
resistance to the
fl
ow of refrigerant system increases, thus lowering cooling capacity. As a result, the
compressor may become defective. Always choose the shortest path and follow the recommendations as
tabulated below:
Outdoor
A5LCY10DR
A5LCY15DR
A5LCY20CR
A5LCY25CR
Indoor
A5WMY10JR
A5WMY15JR
A5WMY20JR
A5WMY25JR
Max. allowable length, m
15
15
30
30
Max. allowable elevation, m
10
10
10
10
Liquid pipe, mm
O.D. 6.4
O.D. 6.4
O.D. 6.4
O.D. 6.4
Gas pipe, mm
O.D. 9.5
O.D. 12.7
O.D. 12.7
O.D. 15.9
Additional charge of refrigerant, g/m
(for piping length above 7.5m)
20
20
20
20
Outdoor
A5LCY10DR
A5LCY15DR
A5LCY20CR
Indoor
A5CKY10CR
A5CKY15CR
A5CKY20CR
Max. allowable length, m
15
15
30
Max. allowable elevation, m
10
10
10
Liquid pipe, mm
O.D. 6.4
O.D. 6.4
O.D. 6.4
Gas pipe, mm
O.D. 9.5
O.D. 12.7
O.D. 12.7
Additional charge of refrigerant, g/m
(for piping length above 7.5m)
20
20
20
Outdoor
A5LCY20CR
A5LCY25CR
Indoor
A5CKY20ER
A5CKY25ER
Max. allowable length, m
30
30
Max. allowable elevation, m
10
10
Liquid pipe, mm
O.D. 6.4
O.D. 6.4
Gas pipe, mm
O.D. 12.7
O.D. 15.9
Additional charge of refrigerant, g/m
(for piping length above 7.5m)
20
20
Outdoor
A5LCY10DR
A5LCY15DR
A5LCY20CR
A5LCY25CR
Indoor
A5CCY10CR
A5CCY15CR
A5CCY20CR
A5CCY25CR
Max. allowable length, m
15
15
30
30
Max. allowable elevation, m
10
10
10
10
Liquid pipe, mm
O.D. 6.4
O.D. 6.4
O.D. 6.4
O.D. 6.4
Gas pipe, mm
O.D. 9.5
O.D. 12.7
O.D. 12.7
O.D. 15.9
Additional charge of refrigerant, g/m
(for piping length above 7.5m)
20
20
20
20
Outdoor
A5LCY15DR
A5LCY20CR
A5LCY25CR
Indoor
A5CMY15ER
A5CMY20ER
A5CMY25ER
Max. allowable length, m
15
30
30
Max. allowable elevation, m
10
10
10
Liquid pipe, mm
O.D. 6.4
O.D. 6.4
O.D. 6.4
Gas pipe, mm
O.D. 12.7
O.D. 12.7
O.D. 15.9
Additional charge of refrigerant, g/m
(for piping length above 7.5m)
20
20
20
* Be sure to add the proper amount of additional refrigerant. Failure to do so may result in reduced performance.
Remark: The refrigerant pre-charged in the outdoor unit is for piping length up to 7.5m.
Summary of Contents for A5CCY-C Series
Page 1: ...Inverter Y Single Split Series I A5LCY_ i A5LCY 10DR A5LCY 15DR A5LCY 20CR A5LCY 25CR Models...
Page 2: ......
Page 25: ...22 A5LCY_ i Wiring Diagram Outdoor Unit Indoor Unit Model A5LCY 20 25CR Model A5WMY 20 25JR...
Page 59: ...A5LCY_ i Sound Data Part Number 000353103N2525 A5CKY 25ER...
Page 65: ...Sound Data A5LCY_ i Part Number 000353103M2525 A5CMY 25ER...