The Scholar 2.0 heat pump or air conditioner should be installed following the instructions
in this manual. After installation, the Scholar 2.0 air box should be from 1-1/4” to 1-3/8”
from the outside surface of the finished wall, as shown in Figure 1.
FREEBLOW PLENUM
SCHOLAR III™
HEAT PUMP OR
AIR CONDITIONER
DISTANCE (INCHES) BETWEEN AIR BOX
AND OUTSIDE FINISHED WALL
LOUVER/COLLAR
OUTSIDE WALL
NOTE: TO PREVENT RAIN WATER FROM RUNNING
DOWN THE INTERIOR OF THE WALL, INSTALL FLASHING UNDER
THE OUTDOOR AIR BOX OVER THE SILL OF THE WALL OPENING.
Figure 1. Dimension between Scholar 2.0 Air Box and Finished Outside Wall for
Outdoor Louver/Collar Assembly Installation.
CAUTION
WHEN FASTENING LOUVER/COLLAR ASSEMBLY TO AIR BOX (OR EXTENSION) DO
NOT OVERTIGHTEN LOUVER SCREWS. OVERTIGHTENING SCREWS WILL CAUSE
DAMAGE AND WARP THE LOUVER/COLLAR ASSEMBLY.
1.04 INSTALLATION OF LOUVER/COLLAR ASSEMBLY, LOUVER AND COLLAR
A. Louver/Collar Assembly
The preassembled louver/collar is fastened from the outside of the building in one
assembly.
1. The louver/collar assembly is
fastened directly to the air box
as shown in
Figure 2, with six screws supplied with the louver/collar. Prior to installing the
louver, apply caulk around the perimeter flange of the outdoor air box. Be careful
not to block the weep holes on the bottom flange. To ensure proper fit up of the
collar to the outside wall surface, be sure the unit is positioned as shown in Figure
1. After the six screws have been installed and appropriately tightened (do not
over torque), the color coordinated screw caps are snapped into place to cover the
screw fastener heads. Provide a water seal around the top & both sides edges of
the collar/wall interface, by applying an even bead of sealant caulk at the collar/wall
interface.
2. The louver/collar assembly is
fastened directly to the outside wall
, as shown in
Figure 2.
B. Louver
The louver itself may be fastened to the air box as shown in Figure 2.
C. Collar
The collar itself may be fastened to the outside wall by following the instructions in Figure 2.