Acromag IntelliPack 801T Series User Manual Download Page 7

IntelliPack Series 801T Transmitter/Alarm User's Manual                                                               mV/TC/RTD Input 
___________________________________________________________________________________________ 
 

 - 7 - 

 

Transmitter/Alarm Programming Procedure…continued 

 
9.     Press the 

“UP”

 or 

“DOWN”

 push-button once.  Refer to 

Functional Block Diagram 4501-689 and note that internally, 
the output of the Range Adjust Box is now set for 100.0% for 
the input full-scale value of 200

C.  The transmitter will 

adjust it’s output to the maximum output value (20.000mA).  
If the output is not exactly at the full-scale level (20.000mA), 
press the UP or DN switches continuously until the desired 
output is achieved.  

Note:

  After first pressing the UP & DN 

push-buttons, they will function as trim adjustments for the 
output stage.  The output trim adjustment should be limited 
to 

10%.  Each successive depression of the “UP” or “DN” 

switch will increment or decrement the output signal by a 
small amount.  Holding the switch depressed will increase 
the amount of increment or decrement. 

10.   Press the 

“SET”

 push-button to accept the full-scale value.  

Note that every time “SET” is pressed, the yellow “Status” 
LED will flash once and the full-scale output will be captured. 

11.   If you are configuring an 801T-0500 model, which has no 

alarm function, then you should skip steps 12-17 and jump 
ahead to step 18. 

12.   Press the 

“MODE”

 push button one time until the yellow 

zero/full-scale LED goes out and the yellow relay LED turns 
ON (see Table 3).  In this mode, the unit is ready to accept 
an input setpoint level for the alarm.  If you do not wish to 
change the setpoint, skip to step 15.  

        

Note:

  The setpoint can be set to any value within the input 

        range selected regardless of the zero/full-scale settings.   
        For example, you can have a setpoint of 300

C with a  

        TC Type J transmitter calibrated for 0-200

C as its nominal  

        range is from -200

C to 760

C. 

13.   Adjust the input source to the High or Low alarm setpoint 

level. 

14.   Press the

 

“SET”

 push button to accept the setpoint.  Note 

that every time the “SET” button is pressed, the yellow 
status LED will flash once and the value at the input will be 
captured. 

15.   Press the 

“MODE”

 push button one time and the yellow 

relay LED should start flashing (see Table 3).  This means 
that the unit is ready to accept the dropout level for the 
alarm relay.  If you do not wish to change the dropout, skip 
to step 18. 

16.   Adjust the input source to the desired dropout level.  
17.   Press the 

“SET”

 push button to accept the input dropout 

level.  Note that every time the “SET” button is pressed, the 
yellow status LED will flash once and the value at the input 
will be captured.  The module will use the difference 
between the setpoint and dropout values to calculate relative 
deadband. 

18.   Press the

 

“MODE”

 push button one time to complete the 

program sequence and return to run mode.  The green 
“RUN” LED will turn ON, the yellow “Zero/Full-Scale” LED 
will be OFF, and the yellow alarm LED will be on or off 
according to the alarm status.  The module will now assume 
a transfer function based on the zero and full-scale values 
just set.  The setpoint and dropout of 801T-1500 units is 
used to determine the alarm deadband.  

Note:

  If no push-

buttons are depressed for a period greater than 3 minutes, 
then the module will automatically revert to run mode (green 
“Run” LED will light) and no changes will be made to the 
original zero, full-scale, and optional setpoint & dropout 
settings. 

 

4.0  THEORY OF OPERATION 

 

Refer to Simplified Schematic 4501-680 and Functional Block 

Diagram 4501-689 to gain a better understanding of the circuit.  
Note that these transmitters will accept a thermocouple, an RTD 
sensor, or a voltage input, and condition it to a voltage signal for 
the A/D converter.  The A/D converter stage then applies 
appropriate gain to the signal, performs analog-to-digital 
conversion, and digitally filters the signal.  The digitized signal is 
then transmitted serially to a microcontroller.  The microcontroller 
completes the transfer function according to the transmitter type 
and its embedded function, and sends a corresponding output 
signal to an optically isolated Digital-to-Analog Converter (DAC).  
The DAC then updates its current or voltage outputs in response.  
The microcontroller also compares the signal value to the limit 
value according to the alarm type and completes all necessary 
alarm functions per its embedded program (801T-1500 units 
only).  The embedded configuration and calibration parameters 
are stored in non-volatile memory integrated within the micro-
controller.  Only the functions required by an application are 
actually stored in memory

—new functionality can be downloaded 

via the IntelliPack Configuration Program and Serial Port Adapter.  
A wide input switching regulator (isolated flyback mode) provides 
is5V power to the circuit, plus an is15V output 
circuit supply.  Refer to Functional Block Diagram 4501-689 for 
an overview of how the software/push-button configuration 
variables are arranged. 

 
 

5.0  SERVICE AND REPAIR 
 

CAUTION:

  Risk of Electric Shock - More than one 

disconnect switch may be required to de-energize the 
equipment before servicing. 

 

SERVICE AND REPAIR ASSISTANCE 

 

This module contains solid-state components and requires no 

maintenance, except for periodic cleaning and transmitter 
configuration parameter (zero, full-scale, setpoint, deadband, etc) 
verification.  Since Surface Mounted Technology (SMT) boards 
are generally difficult to repair, it is highly recommended that a 
non-functioning module be returned to Acromag for repair.  The 
board can be damaged unless special SMT repair and service 
tools are used.  Further, Acromag has automated test equipment 
that thoroughly checks and calibrates the performance of each 
module.  Please refer to Acromag’s Service Policy Bulletin or 
contact Acromag for complete details on how to obtain service 
parts and repair. 
 

PRELIMINARY SERVICE PROCEDURE 
 

Before beginning repair, be sure that all installation and 

configuration procedures have been followed.  The unit routinely 
performs internal diagnostics following power-up or reset.  During 
this period, all LED’s will turn ON momentarily, and the green 
“Run” LED flashes.  If the diagnostics complete successfully, the 
“Run” LED will stop flashing after approximately one second and 
remain ON.  This indicates that the unit is operating normally.  If 
the “Run” LED continues to flash, then this is indicative of a 
problem.

Summary of Contents for IntelliPack 801T Series

Page 1: ...ER S MANUAL ACROMAG INCORPORATED 30765 South Wixom Road P O BOX 437 Wixom MI 48393 7037 U S A Tel 248 295 0880 Fax 248 624 9234 Web http www acromag com Email sales acromag com Copyright 1997 Acromag Inc Printed in the USA Data and specifications are subject to change without notice 8500568J ...

Page 2: ...life is involved It is important that the user employ satisfactory overall system design It is agreed between the Buyer and Acromag that this is the Buyer s responsibility 1 0 INTRODUCTION These instructions cover hardware functionality of the transmitter models listed in Table 1 Supplementary sheets are attached for units with special options or features Table 1 Models Covered in This Manual Seri...

Page 3: ...span calibration plus alarm setpoint and deadband adjustments to be made via module push buttons and LED s thus facilitating in field changes without having to connect a host computer Key IntelliPack 801T Features continued Fully Isolated Input power outputs and relay contacts are all isolated from each other for safety and increased noise immunity Wide Input Transfer Function Variability Proporti...

Page 4: ... and the IntelliPack module IntelliPack Software Interface Package Model 800C SIP The IntelliPack Software Interface Package combines the Configuration Software 5030 881 Alarm Configuration Manual 8500 563 Transmitter Configuration Manual 8500 570 Serial Port Adapter 5030 913 and Cable 5030 902 into a complete kit for interfacing with IntelliPack Alarms and Transmitters 2 0 PREPARATION FOR USE UNP...

Page 5: ...P terminals This jumper is installed at the factory and should be removed for current output applications Be sure to remove power and or disable the load before unplugging the terminals to uninstall the module installing or removing jumpers or before attempting service All connections must be made with power removed CAUTION Risk of Electric Shock More than one disconnect switch may be required to ...

Page 6: ...ssing the push buttons use a blunt tipped object and apply pressure gradually until you feel or hear the tactile response Note The transmitter s input type temperature units sensor break direction CJC on off TC models input wiring RTD models and output range can only be set via the IntelliPack Configuration Program For example use the software to select a Type J thermocouple degrees Celsius units ...

Page 7: ...T 1500 units is used to determine the alarm deadband Note If no push buttons are depressed for a period greater than 3 minutes then the module will automatically revert to run mode green Run LED will light and no changes will be made to the original zero full scale and optional setpoint dropout settings 4 0 THEORY OF OPERATION Refer to Simplified Schematic 4501 680 and Functional Block Diagram 450...

Page 8: ...owing options respectively X 1 with Alarm Relay X 0 without Alarm Relay 5 Output Transmitter Voltage or Current 0 Enclosure DIN rail mount 0 Approvals cULus Listed INPUT SPECIFICATIONS Unit must be wired and configured for the intended input type and range see Installation Section for details The unit can be configured to accept any one of the input types described using the IntelliPack Configurat...

Page 9: ...put Filter Bandwidth 3dB at 3Hz typical Noise Rejection Normal Mode 40dB 60Hz typical with 100 input unbalance Noise Rejection Common Mode 140dB 60Hz typical with 100 input unbalance Analog to Digital Converter A D A 16 bit converter Input Conversion Rate 5 conversions per second Input Filter Normal mode filtering plus digital filtering optimized and fixed per input range within the ADC Table 6 Re...

Page 10: ... NYLON type 6 6 polyamide thermoplastic UL94 V 2 color beige general purpose NEMA Type 1 enclosure Printed Circuit Boards Military grade FR 4 epoxy glass Shipping Weight 1 pound 0 45 Kg packed APPROVALS xxx0 0 Agency Approvals cULus Listed UL File E199702 Warning This product is not approved for hazardous location applications ENVIRONMENTAL SPECIFICATIONS Operating Temperature 25 C to 70 C 13 F to...

Page 11: ...Serial Port Adapter serves as an isolated interface converter between EIA232 and the IntelliPack s SPI port Baud Rate EIA232 19 2K baud SOFTWARE CONFIGURATION Units are fully reprogrammable via our user friendly Windows 95 or NT IntelliPack Configuration Program Model 5030 881 A cable 5030 902 and converter 5030 913 are required to complete the interface Software Interface Package 800C SIP See Dra...

Page 12: ...or jitter on the input signal has the effect of reducing narrowing the instrument s deadband and may produce contact chatter Another long term effect of contact chatter is a reduction in the life of the mechanical relay contacts To reduce this undesired effect increase the deadband setting Visual Alarm Indicator A yellow LED labeled RLY for the relay provides visual status indication of when the r...

Page 13: ...SOR EXCITATION SCREW TERMINAL NUMBER 2 3 2 5 INPUT SIGNAL INPUT RTN IN B CONDITIONING 2 1 2 2 2 4 2 6 TEMP SENSOR MOUNTED IN FIRST TWO POSITIONS OF TERMINAL BL OCK NOTE B JUMPER IN RTN FOR THERMOCOUPL E INPUT TEMP SENSOR REL AY MODEL 801T 1500 UNIT ONLY N O COM N C 4 4 4 5 4 3 NC 4 6 REL AY ISOL ATION RE LA Y OUTPUT ISOL ATION SHIEL D ISOL ATION 4 1 4 2 SHL D OUTP UT S HIE LD OUTP UT INSTAL L JUMP...

Page 14: ...RTD Sensor Millivolts A D RTD Wiring 2 3 4 Wire Analog INPUT type Sensor Trim Z FS TC RTD Linearization T C CJC On Off Digital Process Variable PV Engineering Units Degrees C F K Millivolts Reading on PC Monitor ON OFF Alarm On Off K1 Analog OUTPUT type ALARM OUTPUT BLOCK Alarm Configuration Variables High or Low Limit Alarm Relay Alarm Delay Automatic Reset or Latching Failsafe Non Failsafe Relay...

Page 15: ...NFIGURATION PORT FOR INTELLIPACK MODE SWITCH CABLE SCHEMATIC MODEL 5030 913 MODEL 5030 902 SERIAL PORT ADAPTER TO INTELLIPACK CABLE MODULE CONFIGURATION SEE USER S MANUAL SERIAL ADAPTER RELAY 1 RESET SWITCH RELAY 2 RESET SWITCH STATUS LED YELLOW RELAY 1 LED YELLOW RELAY 2 LED YELLOW NOTE USB COM SERIAL PORTS ARE OS SOFTWARE CONFIGURED ATTACH ADAPTER TO COM1 OR COM2 ON THE PC SERIES 8XXT COMPUTER C...

Page 16: ... SHLD MODE SWITCH ZERO FUL L SCAL E UP RESET SWITCH DOWN RESET SWITCH L ED YEL L OW R LY S T REL AY L ED YEL L OW STATUS L ED YEL L OW SET SWITCH CONFIGURATION PORT FOR MODUL E CONFIGURATION SEE USER S MANUAL R TERMINAL BL OCKS PL UG IN TYPE REMOVABL E NOTE TB2 2 1 2 2 ARE NOT REMOVABL E AND RESERVED FOR THE CJC TEMPERATURE SENSOR DO NOT CONNECT TO THESE TERMINAL S SHIEL DED CABL E INPUT CONNECTIO...

Page 17: ...6 TB 4 TB 3 G R O U N D CONT ACT F IGURE B R ELA Y 46 43 45 N O C O M 35 42 JMP TB 3 PWR 32 34 31 D C V D C 11 14 12 TB 2 22 15 25 23 26 DIODE DC L OAD TB 4 N C MOV AC L OAD TB 4 N C S P D T C O N TA C TS N O N O N C N O RELAY P OW E R O R O U TPU T L 1 S P D T C O N TA C TS T YPICAL DIN RAI L MOUNT ED RELAY INTERPOSING RELAY CONNECTIONS T YPICAL DIN RAI L MOUNT ED RELAY IN DE ENERGI Z ED CONDIT I...

Page 18: ..._________________________________ 18 RUN Acromag RLY S T Z FS 118 9 4 68 95 3 3 75 MODE S E T D IN EN 50022 35mm T R AIL D IN MOU N TIN G C L 2 34 59 4 SC R EWD R IVER SLOT FOR R EMOVAL FR OM T R AIL 4 35 110 5 3 90 99 1 4501 642A NOTE ALL DIMENSION ARE IN INCHES MILLIMETERS R INTELLIPACK TRANSMITTER 1 05 26 7 ENCLOSURE DIMENSIONS ...

Page 19: ..._____________________________________________________________________ 19 REVISION HISTORY The following table details the revision history for this document Release Date Version EGR DOC Description of Revision 3 AUG 2017 J CAP JAA Remove CE Mark due to non RoHS compliant part Refer to ECN 17G016 ...

Page 20: ...IntelliPack Series 801T Transmitter Alarm User s Manual mV TC RTD Input ___________________________________________________________________________________________ 20 Notes ...

Reviews: