background image

IntelliPack Series 801T Transmitter/Alarm User's Manual                                                               mV/TC/RTD Input 
___________________________________________________________________________________________ 
 

 - 6 - 

 

3.0  MODULE CONFIGURATION 

 

This transmitter/alarm module needs to be configured for 

your application.  Configuration is done using Acromag’s 
Windows 95

 or NT

 IntelliPack Configuration Program and 

Serial Port Adapter.  Transmitter calibration and configuration 
details are included in the IntelliPack Transmitter Configuration 
Manual (8500-570).  Field calibration of transmitter zero, full-
scale/span, setpoint, and dropout/deadband via the modu

le’s 

push-

buttons and LED’s is covered in the following paragraphs. 

 

FIELD CALIBRATION/CONFIGURATION 

 

This program mode allows adjustment to key transmitter 

calibration and alarm parameters in the field, without having to 
connect a host computer.  Field reprogrammability of zero & full-
scale (input to output scaling), plus alarm setpoint & deadband 
(Model 801T-1500) is alternately accomplished via the 
transmitter/alarm module’s “SET”, “MODE”, “UP”, and “DOWN” 
push buttons, and the zero/full-scale and relay 

LED’s (see 

Drawing 4501-642). 

 
Equipment Required 

 

An accurate input source (voltage or resistance) adjustable 

over the range required for alarm setpoint and dropout.  A 
thermocouple (or mV source with an ice-point reference) or RTD 
calibrator may also be used.  

Note:

  For best results, the input 

source must be accurate beyond the required specifications.  For 
voltage inputs, use a voltage source with an output impedance of 
100

 or less.  An accurate current or voltage meter is also 

required to monitor the output level.  This meter must be accurate 
beyond the module specifications for best results. 

 

Note:

  

The module’s input range must already be set via the 

IntelliPack Configuration Software.  Input levels outside of the 
configured input range will not be accepted for zero, full-scale, 
setpoint, or dropout calibration.  Since input levels cannot be 
validated during field programming, entering incorrect signals can 
produce an undesired output response.  Install a jumper between 
the output “I+” and “JMP” terminals for voltage output, remove 
this jumper for current output. 
 

Transmitter/Alarm General Field Programming Procedure 

 
The following procedure uses the corresponding zero/full-

scale (labeled “Z/FS”) and relay (labeled “RLY”) LED’s to indicate 
which parameter is being programmed.  A constant ON zero/full-
scale LED refers to zero configuration (scaling input for 0% 
output), a flashing ON/OFF zero/full-scale LED refers to full-
scale/span configuration (scaling input for 100% output).  A 
constant ON relay LED indicates setpoint adjustment, a flashing 
ON/OFF relay LED indicates dropout/deadband adjustment.  
Refer to Table 3. 
 

Table 3: Field Configuration LED Program Indication 

LED INDICATOR 

CONSTANT ON 

FLASHING 

Yellow  

Zero/Full-Scale  

(labeled “Z/FS”) 

 

Zero 

 

Full-Scale 

801T-1500 Only

 

Yellow Relay 

(labeled “RLY”), 

 

High or Low 

Setpoint 

 

High or Low 

Dropout 

 

CAUTION:

  Do not insert sharp or oversized objects into the 

switch openings as this may damage the unit.  When depressing 
the push-buttons, use a blunt tipped object and apply pressure 
gradually until you feel or hear the tactile response. 
 

Note:

 

The transmitter’s input type, temperature units, sensor 

break direction, CJC on/off (TC models), input wiring (RTD 
models), and output range can only be set via the IntelliPack 
Configuration Program.  For example, use the software to select 
a Type J thermocouple, degrees Celsius units, CJC ON, a normal 
acting 4 to 20mA output.  You may use field program mode to 
scale virtually any part of the input range to the selected output 
range via the front panel push buttons.  For example, use the 0 to 
200

C portion of the type J TC input to drive the 4 to 20mA output 

range--this configuration will be used as an example range in the 
following procedure. 
 

IMPORTANT:

  You must allow the unit to warm-up, powered and 

oriented as in its final application, for at least 5 minutes prior to 
calibrating the unit.  Failure to warm the unit prior to calibration 
may result in measurement error. 
 
1.     Connect a precise voltage source; thermocouple calibrator, 

or RTD calibrator to the input, as required (refer to Electrical 
Connections Drawing 4501-681).  Also, according to the 
module’s output configuration, connect a precise current or 
volt meter to read the 

transmitter’s output signal. 

2.     

Apply power and the module’s green “Run” LED will light. 

3.     Press and hold the 

“MODE”

 push button until the green 

“Run” LED turns OFF and the yellow “Zero/Full-Scale” LED 
turns ON.  In this mode, the unit is ready to accept a zero 
input for the transmitter (equivalent to the scaling input for 
0% output).  If you do not wish to change the zero 
parameter, skip to step 7. 

4.     Adjust the input source to the zero value (this value must be 

within the input range selected).  For our example: use 0

C. 

5.     Press the 

“UP”

 or 

“DOWN”

 push-button once.  Refer to 

Functional Block Diagram 4501-689 and note that internally, 
the output of the Range Adjust Box is now set for 0.0% for 
the input zero value of 0

C.  The transmitter will adjust it’s 

output to the minimum output value (4.000mA).  If the 
measured output is not exactly at the zero level (4.000mA), 
press the UP or DN switches continuously until the desired 
output is achieved. 

Note: 

 After first pressing the UP & DN push-buttons, they 

will function as trim adjustments for the output stage.  The 
output trim adjustment should be limited to 

10%.  Each 

successive depression of the “UP” or “DN” switch will 
increment or decrement the output signal by a small 
amount.  Holding the switch depressed will increase the 
amount of increment or decrement. 

6.     Press the

 

“SET”

 push-button to accept the zero value.  

Note that every time “SET” is pressed, the yellow “Status” 
LED will flash once and the zero output will be captured. 

7.     Press the 

“MODE”

 push button one time.  The yellow 

“Zero/Full-Scale” LED will flash on/off, indicating that the unit 
is ready to accept the full-scale value (equivalent to the 
scaling input for 100% output).  If you do not wish to change 
this parameter, skip to step 11. 

8.     Adjust the input source to the full-scale value (the input 

value must be within the input range selected).  For 
example: 200

C.  

Note:

  The full-scale value must be 

greater than the zero value.  If the zero and full-scale points 
are too close together, performance will be degraded. 

Summary of Contents for IntelliPack 801T Series

Page 1: ...ER S MANUAL ACROMAG INCORPORATED 30765 South Wixom Road P O BOX 437 Wixom MI 48393 7037 U S A Tel 248 295 0880 Fax 248 624 9234 Web http www acromag com Email sales acromag com Copyright 1997 Acromag Inc Printed in the USA Data and specifications are subject to change without notice 8500568J ...

Page 2: ...life is involved It is important that the user employ satisfactory overall system design It is agreed between the Buyer and Acromag that this is the Buyer s responsibility 1 0 INTRODUCTION These instructions cover hardware functionality of the transmitter models listed in Table 1 Supplementary sheets are attached for units with special options or features Table 1 Models Covered in This Manual Seri...

Page 3: ...span calibration plus alarm setpoint and deadband adjustments to be made via module push buttons and LED s thus facilitating in field changes without having to connect a host computer Key IntelliPack 801T Features continued Fully Isolated Input power outputs and relay contacts are all isolated from each other for safety and increased noise immunity Wide Input Transfer Function Variability Proporti...

Page 4: ... and the IntelliPack module IntelliPack Software Interface Package Model 800C SIP The IntelliPack Software Interface Package combines the Configuration Software 5030 881 Alarm Configuration Manual 8500 563 Transmitter Configuration Manual 8500 570 Serial Port Adapter 5030 913 and Cable 5030 902 into a complete kit for interfacing with IntelliPack Alarms and Transmitters 2 0 PREPARATION FOR USE UNP...

Page 5: ...P terminals This jumper is installed at the factory and should be removed for current output applications Be sure to remove power and or disable the load before unplugging the terminals to uninstall the module installing or removing jumpers or before attempting service All connections must be made with power removed CAUTION Risk of Electric Shock More than one disconnect switch may be required to ...

Page 6: ...ssing the push buttons use a blunt tipped object and apply pressure gradually until you feel or hear the tactile response Note The transmitter s input type temperature units sensor break direction CJC on off TC models input wiring RTD models and output range can only be set via the IntelliPack Configuration Program For example use the software to select a Type J thermocouple degrees Celsius units ...

Page 7: ...T 1500 units is used to determine the alarm deadband Note If no push buttons are depressed for a period greater than 3 minutes then the module will automatically revert to run mode green Run LED will light and no changes will be made to the original zero full scale and optional setpoint dropout settings 4 0 THEORY OF OPERATION Refer to Simplified Schematic 4501 680 and Functional Block Diagram 450...

Page 8: ...owing options respectively X 1 with Alarm Relay X 0 without Alarm Relay 5 Output Transmitter Voltage or Current 0 Enclosure DIN rail mount 0 Approvals cULus Listed INPUT SPECIFICATIONS Unit must be wired and configured for the intended input type and range see Installation Section for details The unit can be configured to accept any one of the input types described using the IntelliPack Configurat...

Page 9: ...put Filter Bandwidth 3dB at 3Hz typical Noise Rejection Normal Mode 40dB 60Hz typical with 100 input unbalance Noise Rejection Common Mode 140dB 60Hz typical with 100 input unbalance Analog to Digital Converter A D A 16 bit converter Input Conversion Rate 5 conversions per second Input Filter Normal mode filtering plus digital filtering optimized and fixed per input range within the ADC Table 6 Re...

Page 10: ... NYLON type 6 6 polyamide thermoplastic UL94 V 2 color beige general purpose NEMA Type 1 enclosure Printed Circuit Boards Military grade FR 4 epoxy glass Shipping Weight 1 pound 0 45 Kg packed APPROVALS xxx0 0 Agency Approvals cULus Listed UL File E199702 Warning This product is not approved for hazardous location applications ENVIRONMENTAL SPECIFICATIONS Operating Temperature 25 C to 70 C 13 F to...

Page 11: ...Serial Port Adapter serves as an isolated interface converter between EIA232 and the IntelliPack s SPI port Baud Rate EIA232 19 2K baud SOFTWARE CONFIGURATION Units are fully reprogrammable via our user friendly Windows 95 or NT IntelliPack Configuration Program Model 5030 881 A cable 5030 902 and converter 5030 913 are required to complete the interface Software Interface Package 800C SIP See Dra...

Page 12: ...or jitter on the input signal has the effect of reducing narrowing the instrument s deadband and may produce contact chatter Another long term effect of contact chatter is a reduction in the life of the mechanical relay contacts To reduce this undesired effect increase the deadband setting Visual Alarm Indicator A yellow LED labeled RLY for the relay provides visual status indication of when the r...

Page 13: ...SOR EXCITATION SCREW TERMINAL NUMBER 2 3 2 5 INPUT SIGNAL INPUT RTN IN B CONDITIONING 2 1 2 2 2 4 2 6 TEMP SENSOR MOUNTED IN FIRST TWO POSITIONS OF TERMINAL BL OCK NOTE B JUMPER IN RTN FOR THERMOCOUPL E INPUT TEMP SENSOR REL AY MODEL 801T 1500 UNIT ONLY N O COM N C 4 4 4 5 4 3 NC 4 6 REL AY ISOL ATION RE LA Y OUTPUT ISOL ATION SHIEL D ISOL ATION 4 1 4 2 SHL D OUTP UT S HIE LD OUTP UT INSTAL L JUMP...

Page 14: ...RTD Sensor Millivolts A D RTD Wiring 2 3 4 Wire Analog INPUT type Sensor Trim Z FS TC RTD Linearization T C CJC On Off Digital Process Variable PV Engineering Units Degrees C F K Millivolts Reading on PC Monitor ON OFF Alarm On Off K1 Analog OUTPUT type ALARM OUTPUT BLOCK Alarm Configuration Variables High or Low Limit Alarm Relay Alarm Delay Automatic Reset or Latching Failsafe Non Failsafe Relay...

Page 15: ...NFIGURATION PORT FOR INTELLIPACK MODE SWITCH CABLE SCHEMATIC MODEL 5030 913 MODEL 5030 902 SERIAL PORT ADAPTER TO INTELLIPACK CABLE MODULE CONFIGURATION SEE USER S MANUAL SERIAL ADAPTER RELAY 1 RESET SWITCH RELAY 2 RESET SWITCH STATUS LED YELLOW RELAY 1 LED YELLOW RELAY 2 LED YELLOW NOTE USB COM SERIAL PORTS ARE OS SOFTWARE CONFIGURED ATTACH ADAPTER TO COM1 OR COM2 ON THE PC SERIES 8XXT COMPUTER C...

Page 16: ... SHLD MODE SWITCH ZERO FUL L SCAL E UP RESET SWITCH DOWN RESET SWITCH L ED YEL L OW R LY S T REL AY L ED YEL L OW STATUS L ED YEL L OW SET SWITCH CONFIGURATION PORT FOR MODUL E CONFIGURATION SEE USER S MANUAL R TERMINAL BL OCKS PL UG IN TYPE REMOVABL E NOTE TB2 2 1 2 2 ARE NOT REMOVABL E AND RESERVED FOR THE CJC TEMPERATURE SENSOR DO NOT CONNECT TO THESE TERMINAL S SHIEL DED CABL E INPUT CONNECTIO...

Page 17: ...6 TB 4 TB 3 G R O U N D CONT ACT F IGURE B R ELA Y 46 43 45 N O C O M 35 42 JMP TB 3 PWR 32 34 31 D C V D C 11 14 12 TB 2 22 15 25 23 26 DIODE DC L OAD TB 4 N C MOV AC L OAD TB 4 N C S P D T C O N TA C TS N O N O N C N O RELAY P OW E R O R O U TPU T L 1 S P D T C O N TA C TS T YPICAL DIN RAI L MOUNT ED RELAY INTERPOSING RELAY CONNECTIONS T YPICAL DIN RAI L MOUNT ED RELAY IN DE ENERGI Z ED CONDIT I...

Page 18: ..._________________________________ 18 RUN Acromag RLY S T Z FS 118 9 4 68 95 3 3 75 MODE S E T D IN EN 50022 35mm T R AIL D IN MOU N TIN G C L 2 34 59 4 SC R EWD R IVER SLOT FOR R EMOVAL FR OM T R AIL 4 35 110 5 3 90 99 1 4501 642A NOTE ALL DIMENSION ARE IN INCHES MILLIMETERS R INTELLIPACK TRANSMITTER 1 05 26 7 ENCLOSURE DIMENSIONS ...

Page 19: ..._____________________________________________________________________ 19 REVISION HISTORY The following table details the revision history for this document Release Date Version EGR DOC Description of Revision 3 AUG 2017 J CAP JAA Remove CE Mark due to non RoHS compliant part Refer to ECN 17G016 ...

Page 20: ...IntelliPack Series 801T Transmitter Alarm User s Manual mV TC RTD Input ___________________________________________________________________________________________ 20 Notes ...

Reviews: