BusWorks® 965EN Module User’s Manual Modbus TCP/IP mV/TC Input
___________________________________________________________________
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:
33
Ref
Addr.
Description
Data Type/Format
Input Registers (3x References, Read-Only)
3
0013
000C
CH00 Value
±20000 (Voltage input range) or
Temperature (ºC)
3
0014
000D
CH01 Value
±20000 (Voltage input range) or
Temperature (ºC)
3
0015
000E
CH02 Value
±20000 (Voltage input range) or
Temperature (ºC)
3
0016
000F
CH03 Value
±20000 (Voltage input range) or
Temperature (ºC)
3
0017
0010
CH04 Value
(965EN-
4006)
±20000 (Voltage input range) or
Temperature (ºC)
3
0018
0011
CH05 Value
(965EN-
4006)
±20000 (Voltage input range) or
Temperature (ºC)
3
0019
0012
Temp Ref 0
Value
(CJC0)
Temperature (ºC)
3
0020
0013
Temp Ref 1
Value
(CJC1)
Temperature (ºC)
3
0021
0014
Temp Ref 2
Value
(CJC2)
(965EN-
4006)
Temperature (ºC)
3
0028
001B
CJC0 Count
Raw A/D Count Value
3
0029
001C
CJC1 Count
Raw A/D Count Value
3
0030
001D
CJC2 Count
(965EN-
4006)
Raw A/D Count Value
Holding Registers (4x References, Read/Write)
40001
0000
Input Range
(CH 0,1,2 )
Bits 15-4:
0 (Not Used)
Bits 3,2,1,0:
Input Range 0-9
0000
0 - J TC (ºC)
0001
1 - K TC (ºC)
0010
2 - T TC (ºC)
0011
3 - R TC (ºC)
0100
4 - S TC (ºC)
0101
5 - E TC (ºC)
0110
6 - B TC (ºC)
0111
7 - N TC (ºC)
1000
8 - ±100mV DC
1001
9 - ±1V DC
1010-1111
Reserved
4
0002
0001
Input Range
(CH 3,4,5 )
Format is same as Above.
4
0003
0002
CJC Control
(CH 0, 1, 2)
Bits 15-1:
0 (Not Used)
Bit 0:
0=CJC ON, 1=CJC OFF
4
0004
0003
CJC Control
(CH 3, 4, 5)
Bits 15-1:
0 (Not Used)
Bit 0:
0=CJC ON, 1=CJC OFF
Register Map
Model 965EN-4006
Model 965EN-4004
Note: Changes to Holding
Registers take effect
immediately.