BusWork® 965EN Module User’s Manual Modbus TCP/IP mV/TC Input
__________________________________________________________________
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:
44
Note:
Channels 0, 1, & 2, and channels 3, 4, & 5 (every group of 3
channels) must share the same input configuration, but this
configuration may vary between the two groups. Break detection detent
applies to all channels together. CJC 0 is used for channels 0 & 1, CJC
1 for channels 2 & 3, and CJC 2 for channels 4 & 5. All
parameterization bytes take effect immediately.
Dimensions:
1.05 inches wide, 4.68 inches tall, 4.35 inches deep. Refer to
the dimensions drawing at the front of this manual.
DIN Rail Mount:
Type EN50022; “T” rail (35mm).
I/O Connectors:
Removable plug-in type terminal blocks rated for
15A/300V; AWG #12-24 stranded or solid copper wire.
Network Connector:
8-pin RJ-45 connector socket with metal shield
(shield is bypassed to earth ground at the GND terminal via an isolation
capacitor and TVS). Connections are wired MDI, as opposed to MDI-X.
You must use a CAT-5 crossover cable to connect this module to a PC.
Otherwise you may use an auto-crossing Ethernet switch, such as the
Acromag 900EN-S005 to make connections.
RJ-45
Signal (MDI)
Description
1
Tx+
Transmit Positive
2
Tx-
Transmit Negative
3
Rx+
Receive Positive
4
Not Used
Connects to Pin 5
5
Not Used
Connects to Pin 4
6
Rx-
Receive Negative
7
Not Used
Connects to Pin 8
8
Not Used
Connects to Pin 7
Case Material:
Self-extinguishing NYLON type 6.6 polyamide thermoplastic
UL94 V-2, color beige; general purpose NEMA Type 1 enclosure.
Printed Circuit Boards:
Military grade FR-4 epoxy glass.
Shipping Weight:
1 pound (0.45 Kg) packed.
Safety Approvals:
: UL Listed (USA & Canada). Hazardous Locations-
Class I, Division 2, Groups A, B, C, D. Consult factory.
ATEX Certified:
Assessment by TUV Rheinland of North of America, Inc.
per
ATEX Directive 94/9/EC.
Ex nA IIC T4 Gc
TUVNA 14 EX 0001X
X = Special Conditions
1)
“WARNING-EXPLOSION HAZARD-DO NOT MAKE OR BREAK
CONNECTIONS IN HAZARDOUS LOCATIONS OR AREAS”
2)
“Warning: Must be installed in suitable enclosure with an Ingress
Protection of IP54 minimum,
in Hazardous Locations or Areas”
Operating Temperature:
-25
C to +70
C (-13
F to +158
F).
Storage Temperature:
-40
C to +85
C (-40
F to +185
F).
Relative Humidity:
5 to 95%, non-condensing.
Power Requirements:
15-36V DC SELV (Safety Extra Low Voltage).
Observe proper polarity. See table for current.
General Specifications
Enclosure & Physical
Agency Approvals
Environmental
CAUTION: Do not exceed
36VDC peak, to avoid damage
to the module.