BusWork® 965EN Module User’s Manual Modbus TCP/IP mV/TC Input
__________________________________________________________________
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:
6
45 44
42 41
33
D
C
+
31
12 13
15 16
21
23 24
26
T
B
1
G
N
D
46
43
P W R
D
C
-
32
11
14
22
T
B
4
25
T
B
3
T
B
3
PUSH
T
B
2
"T" TYPE
DIN RAIL
Any Series 9XXEN Ethernet Module
PUSH SCREWDRIVER AS SHOWN
TO TILT AND LIFT MODULE OFF RAIL
Remove Terminal Blocks On This
Side To Provide Clearance
MODULE REMOVAL
FROM DIN RAIL
PRY WITH SCREWDRIVER
INSERTED IN SLOT HERE
(DO NOT TWIST TO AVOID
DAMAGING PLASTIC TAB)
USE YOUR FINGER TO APPLY
DOWNWARD PRESSURE HERE
AS YOU LIFT AND TILT MODULE
TO REMOVE IT FROM RAIL
6
3
7
4
8
5
1
2
8
Receive -
R
SPEED
1
1
DISTANCE
Not Used
Not Used
Not Used
Not Used
Transmit -
Tr
10Base-T
100Base-TX
100M
100M
8
CABLE
ETHERNET PORT
CAT 3, CAT 4, or CAT 5 UTP
CAT 5/5e UTP/STP
CLIP
RJ-45 CONNECTOR
RJ45 MDI CONNECTIONS
When attaching the module to the
T-type DIN rail, angle the top of the
unit towards the rail and locate the
top groove of the adapter over the
upper lip of the rail. Firmly push the
unit towards the rail until it snaps into
place. To remove, first separate the
input terminal block(s) from the
bottom side of the module to create a
clearance to the DIN mounting area.
Next, while holding the module in
place from above, insert a
screwdriver into the lower arm of the
DIN rail connector and use it as a
lever to force the connector down
until the unit disengages from the rail
(do not twist the screwdriver to avoid
damaging plastic).
The Ethernet port of this module is wired MDI and does not include
automatic crossover. The Ethernet port of your PC is also wired MDI and
may not include automatic crossover. As such, you must use a crossover
cable like that shown below when connecting this device directly to a PC.
1
1
3
6
1
6
2
3
1
8
2
8
1
8
8
1
PINS: 1 TO 3
2 TO 6
3 TO 1
6 TO 2
RJ45 (Clip Side Down)
RJ45 (Clip Side Down)
FOR DIRECT PC TO
ETHERNET MODULE
CONNECTIONS
CROSSOVER CABLE
FOR MDI TO MDI
OR MDI-X TO MDI-X
CROSSOVER
CONNECTIONS
CONNECTIONS
DIN-Rail
Mounting & Removal
Network
For 100Base-TX systems, use
data grade Unshielded
Twisted-Pair (UTP) wiring that
has a 100Ω characteristic
impedance and meets the
EIA/TIA Category Five wire
specifications.
It is recommended that you
use a crossover CAT-5/5E
cable to connect this device to
your PC.
For 10Base-T systems, you
may use Category 3, Category
4, or Category 5/5E UTP/STP
cable.
In either case, you are limited
to 100 meters between any
two devices.
A crossover cable simply
connects the differential
transmit pair on each end, to
the receive pair on the
opposite end.
Use a standard (direct) cable
when connecting to a hub or
switch port, which are
generally wired MDI-X.