BusWorks® 

961/962PB Module User’s Manual            ProfiBus Differential I/V Input 

__________________________________________________________________ 

 

_______________________________________________________________________________________ 
Acromag, Inc.   Tel:248-624-1541  Fax:248-624-9234   Email:

[email protected]

  http://www.acromag.com 

 

-

-

IN

P

U

T

S

 0

1

IN

P

U

T

S

 0

1

1616 IN1-

IN1-

1515 IN1+

IN1+

1313 IN0+

IN0+

1212

1616

1414 IN0-

1313

1111

+

+

V

I

SHIELDED
CABLE

SHIELDED
CABLE

1414 IN0-

1111

1515 IN1+

IN1+

IN1-

IN1-

1212

IN0+

IN0+

NOT E 1

TB1

DC

TB1

DC

VOLTAGE

CURRENT

(962PB)

(961PB)

Ranges: 0-20mA, 4-20mA,
0-11.17mA, 0-1mA DC.

NOTE 1:  THIS GROUND CONNECTION IS RECOMMENDED FOR BEST
RESULTS.  IF SENSORS ARE INHERENTLY CONNECTED TO GROUND,
USE CAUTION AND AVOID MAKING ADDITIONAL GROUND CONNECTIONS
WHICH COULD GENERATE GROUND LOOPS AND MEASUREMENT ERROR.

Ranges:   +10V,  +5V,
+2.5V,  +1.25V,
+625mV,  +313mV,
+156mV,  +78mV.

on

of f

RUN

RUN

BUS

RUN

BUS

on

BUS

on

of f

BUS

on

RUN

on

of f

RUN

of f

of f

500Kbps

19.2Kbps

400M

1200M

NODE 32'

PRO FI BUS

BUS

A cr om ag

on

of f

PRO FI BUS

A cr om ag

on

A cr om ag

RUN

A cr om ag

PRO FI BUS

RUN

A cr om ag

BUS

A cr om ag

PRO FI BUS

BUS

A cr om ag

12Mbps

9600bps

93.75Kbps

187.5Kbps

100M

1200M

1000M

1200M

RS485 SIGNAL
REPEATER

of f

1

PRO FI BUS

PRO FI BUS

PRO FI BUS

1.5Mbps

BAUD

200M

LENGTH

61

NODE 2'

NODE 5

NODE 31

NETWORK LENGTH PER
BAUD RATE w/ TYPE A
PROFIBUS CABLE

END OF NETWORK
(TERMINATION ON)

TERMINATION
SWITCH

NODE 2

NODE 1

START OF NETWORK
(TERMINATION REQD)

PROFIBUS MASTER
PLUG-IN CARD
INSTALLED IN PC.

START OF SEGMENT
(TERMINATION ON)

NODE 32

NODE 1'

2

NODE 4

NODE 3

3

31

SEGMENT 2 (UP TO 1200 METERS,
UP TO 32 NODES PER SEGMENT)

4

30

NOTE: THE PROFIBUS CONNECTORS SHOWN HAVE A TERMINATION NETWORK BUILT-IN.
WITH TERMINATION ON, THE OUTGOING CABLE IS DISCONNECTED FROM NETWORK.  SWITCH
TERMINATION ON ONLY AT THE BEGINNING AND END OF A NETWORK OR NETWORK SEGMENT.

SEGMENT 1 (UP TO 1200 METERS, UP TO 32 NODES PER SEGMENT)

END OF SEGMENT
(TERMINATION ON)

PROFIBUS MASTER - A
HOST PC WITH PROFIBUS
CARD INSTALLED AND
RUNNING APPLICATION
SOFTWARE.

PROFIBUS RS485 NETWORK

A network segment may contain up to 32 nodes without the use of a signal repeater.
Transmission distance is up to 1200 meters per segment without a repeater.
Termination must be placed at both ends of a network or network-segment.
  
The total number of nodes and total distance may be extended by using signal repeater(s).
The maximum number of modules possible is further limited by the address range from 0 to 125.

+

33 GND

DC-

32

TB3

TB3

L

S

D

M

S

D

  

 S

L

A

V

E

A

D

D

R

E

S

S

  

 (

H

E

X

)

DC+

31

P

W

R

12 TO 36VDC

OBSERVE PROPER POLARITY

  EARTH
GROUND

INPUT POWER
IS ISOLATED

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Connect 12-36V DC to the power terminals labeled DC+ & DC-.  
Observe proper polarity.  For supply connections, use No. 14 AWG 
wires rated for at least 75

C.  

CAUTION:

  Do not exceed 36VDC peak. 

 

 

 
 
 
 
 
 
 

 

IMPORTANT 

– External Fuse:

  If unit is powered from a supply capable of 

delivering more than 1A to the unit, it is recommended that this current be 
limited via a high surge tolerant fuse rated for a maximum current of 1A or 
less (for example, see Bel Fuse MJS1). 

 

 

Connect analog input signals to the input terminals as shown below 
according to your signal type. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

Network 

Example ProfiBus System 
Connections 

Up to 125 slave modules may 
network together with a class 1 
master using four repeaters 
(one repeater every 31 nodes).  
Address 0 is typically reserved 
for the class 1 master. 
 
Note: 12Mbps installations 
require a minimum cable 
length of 1M between stations. 

 
TIP:  A recommended RS485 
repeater for ProfiBus is the 
Siemens 6ES79720AA01-
0XA0. 

 
Power 

Voltage 

Current

 

12VDC 

195mA 

15VDC 

146mA 

24VDC 

91mA 

36VDC 

67mA 

CAUTION:  Risk of Electric 
Shock 

– More than one 

disconnect switch may be 
required to de-energize the 
equipment before servicing. 

Analog Inputs 

 
Input is DC current (961PB), 
or DC voltage (962PB), 
according to model number. 
 
Inputs are not isolated 
channel-to-channel, except for 
small common mode voltages 
up to ±4V peak. 

Summary of Contents for 961PB-2006

Page 1: ...rent Inputs Model 962PB 2006 Six Differential Voltage Inputs USER S MANUAL ACROMAG INCORPORATED Tel 248 624 1541 30765 South Wixom Road Fax 248 624 9234 Wixom MI 48393 2417 U S A Copyright 2002 Acroma...

Page 2: ...Troubleshooting Tools 9 Using Connectors To Troubleshoot 10 Diagnostics Function 10 Diagnostics Table 10 CALIBRATION 11 TECHNICAL REFERENCE KEY FEATURES 13 HOW IT WORKS 14 SPECIFICATIONS 15 Model Num...

Page 3: ...MINAL BLOCKS PROFIBUS CONNECTOR DB9 FEMALE PROF IBUS Acromag RUN PWR LED GREEN SLAVE ADDRESS HEX TB3 DP SLAVE ADDRESS SWITCHES REMOVABLE INPUTS 0 1 IN4 44 41 33 PWR NETWORK 13 IN0 16 IN1 21 5V 24 IN2...

Page 4: ...dress 126 cannot be used in data exchange mode and is reserved for commissioning purpose only You must use the Set Slave Address command to change the internal EEPROM address following power up in ord...

Page 5: ...the length indicated below for your transmission rate For baud rates not shown the lower length of the closest range end points apply i e 100M at 3Mbps Bus Segment Length Limit Per Baud Rate For Type...

Page 6: ...AND END OF A NETWORK OR NETWORK SEGMENT SEGMENT 1 UP TO 1200 METERS UP TO 32 NODES PER SEGMENT END OF SEGMENT TERMINATION ON PROFIBUS MASTER A HOST PC WITH PROFIBUS CARD INSTALLED AND RUNNING APPLICAT...

Page 7: ...IN1 TB1 DIFFERENTIAL CURRENTMONITORING INP Temperature Pressure Level Flow Speed 961PB DCS PLC NOTE 961PB INPUTS ARE NOT ISOLATED CHANNEL TO CHANNEL EXCEPT FOR COMMON MODE VOLTAGES LESS THAN 5V AS SUC...

Page 8: ...oes not include an earth ground screw it may be necessary to strip the cable insulation near the field device and clamp the cable shield to a local grounding bar or surface as shown Connect Earth Grou...

Page 9: ...nd Held ProfiBus Network Maintenance Tools Manufacturer Part Number Special Features Siemens BT 200 Primarily a Cable Tester Comsoft NetTest II Set 4000 7 06C J Includes DP Mono Master Functionality I...

Page 10: ...ort this command and can read the diagnostic information from the Profibus device SYMPTOM POSSIBLE CAUSE POSSIBLE FIX Yellow BUS LED does not light Initialization Problem LED ON if module in data exch...

Page 11: ...one for normal operation and another for accomplishing calibration The normal data exchange definition supports 6 input words 12 input bytes representing your measured values A second calibration def...

Page 12: ...3 6 for the other channels of the same range 8 With user parameter bytes 0 1 select the next range to be calibrated Note 961PB The 4 20mA range is calibrated when the 0 20mA range is calibrated and i...

Page 13: ...model number Range Variability The first 3 channels must share the same range but this can be different than the range of the last 3 channels Optional AC Current Input 961PB Only An optional AC curre...

Page 14: ...4 9 current sink resistors across the inputs Voltage input models use 10 1 precision resistor voltage dividers at the input A multiplexer is used to connect each input voltage to an A D converter sepa...

Page 15: ...figurable for 0 to 20mA 4 20mA 0 11 17mA and 0 1mA DC nominal input ranges A precision 24 9 current sink resistor converts the input current to a voltage that is processed by the A D converter An opti...

Page 16: ...s except 0 1mA This includes the effects of repeatability terminal point conformity and linearization but does not include sensor error Measurement Temperature Drift Better than 50ppm C 0 005 C Analog...

Page 17: ...0 01 of output span per volt peak to peak of power supply ripple Isolation Input channels as a group power and network circuits are isolated from each other for common mode voltages up to 250VAC or 3...

Page 18: ...ty for Class I Division 2 WARNING EXPLOSION HAZARD Do not disconnect equipment unless power has been switched off or the area is known to be non hazardous Interface Standard 3 wire RS 485 multi drop h...

Page 19: ...the Set Slave Address command before completing initialization and assuming the data exchange mode IMPORTANT Address Setting The internal EEPROM address setting and external switch setting is 126 from...

Page 20: ...ive low inputs a value of 1 means the input is ON active low near 0V while a value of 0 specifies the input is OFF or in its high state usually 0V This model includes three user parameterization bytes...

Page 21: ...ory The following table shows the revision history for this document Release Date Version EGR DOC Description of Revision 03 APR 03 A BC KLK Initial release 28 OCT 03 B BC KLK UL updates per ECN 03J02...

Reviews: