background image

BusWorks® 

961/962PB Module User’s Manual            ProfiBus Differential I/V Input 

__________________________________________________________________ 

 

_______________________________________________________________________________________ 
Acromag, Inc.   Tel:248-624-1541  Fax:248-624-9234   Email:

[email protected]

  http://www.acromag.com 

 

on

R

off

In

s

u

l

A

on

OUT

R

off

CABLE
SHIELD

CABLE
SHIELD

INP

GROUND
CLAMP

B

G

rn

PROFIBUS
CONNECTOR

GROUNDING:

ACROMAG MODULES:

THE SHIELD IS COMMON TO
THE HOUSING (FOR METAL
ENCLOSURES).

EARTH GROUND SCREW
ON EQUIPMENT (WHEN
AVAILABLE)

PROFIBUS FIELD DEVICE

EQUIPOTENTIAL BONDING STRIP
(IF NECESSARY--SEE NOTE)

Green Wire = A
Red Wire = B

Use ProfiBus cable
per DIN 19245 and
EN 50170.

PVC
Sheath

R

e

d

GROUND
CLAMP

Use only approved cables
with braided shields of
density greater than 80%.

PROFIBUS
CONNECTOR

S

h

ld

PROFIBUS CABLE

THE SHIELD IS COMMON TO
THE HOUSING (FOR METAL
ENCLOSURES).

PROFIBUS FIELD DEVICE

PROFIBUS WIRING AND GROUND

NOTE:  If a potential difference exists between
earth grounding points, an equalization current
can flow through the cable shield when connected
at both ends.  In this case, it may be necessary to
install an additional potential equalization line between
field locations to minimize this current as shown here.

The metal shroud of the DB9 ProfiBus connector on
Acromag modules is common to pin 1 of the DB9
connector (SHIELD).  This is also common to the
cable shield which must be earth grounded.  Acromag
modules are enclosed in plastic and do not
provide a dedicated earth ground screw.  As such,
a local earth ground connection to the cable shield
must be made as shown above.

EARTH GROUND SCREW
ON EQUIPMENT (WHEN
AVAILABLE)

1.   Always connect the cable shield to earth ground at both
      ends as shown.
2.   If the field device does not include an earth ground
      screw, it may be necessary to strip the cable insulation
      near the field device and clamp the cable shield to a local
      grounding bar or surface as shown.

 

 

Connect Earth Ground as shown in the connection drawings above.  
Additionally, ground the ProfiBus cable as shown in the drawing below. 

 

The ground connections noted are recommended for best results.  If 
sensors are already grounded, use caution and avoid making additional 
ground connections which could create ground loops. 
 

The plastic module housing does not require earth ground. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

The module routinely performs internal diagnostics following power-up 

or reset.  During this period, the gr

een “Run” LED will flash for a moment.  If 

the diagnostics complete OK, the “Run” LED will stop flashing after a few 
seconds and remain ON.  This indicates the unit is operating normally.  
Once the unit has passed through the initialization, parameterization, and 
configuration states, and is in data exchange mode, the yellow BUS LED will 
be ON.  If the BUS LED is OFF and the unit is connected to the network, 
then this may be indicative of an initialization problem (check the address 
setting). 
 

 

Follow the ProfiBus installation guidelines. 

 

Use the recommended cable and connectors of the standard. 

 

Verify that none of the wires are broken or shorted. 

 

Don’t mix the A & B lines.  Use green wire for A and red wire for B. 

 

Do not exceed the recommended segment length for the baud rate. 

 

Make sure that there are no more than 32 RS-485 devices per 
segment (including the master device and the repeater).   

 

Check for proper termination of all copper-wire network segments 
(an RS-485 segment must have a termination resistor at both ends 
of the segment only). 

Earth Ground 

Warning:

  To comply with 

safety and performance 
standards, use shielded cable 
and connect earth ground as 
noted.  Failure to use good 
wiring and grounding practices 
may be unsafe and hurt 
performance. 

TROUBLE-
SHOOTING 

Tips For Building 
ProfiBus Networks 

Summary of Contents for 961PB-2006

Page 1: ...rent Inputs Model 962PB 2006 Six Differential Voltage Inputs USER S MANUAL ACROMAG INCORPORATED Tel 248 624 1541 30765 South Wixom Road Fax 248 624 9234 Wixom MI 48393 2417 U S A Copyright 2002 Acroma...

Page 2: ...Troubleshooting Tools 9 Using Connectors To Troubleshoot 10 Diagnostics Function 10 Diagnostics Table 10 CALIBRATION 11 TECHNICAL REFERENCE KEY FEATURES 13 HOW IT WORKS 14 SPECIFICATIONS 15 Model Num...

Page 3: ...MINAL BLOCKS PROFIBUS CONNECTOR DB9 FEMALE PROF IBUS Acromag RUN PWR LED GREEN SLAVE ADDRESS HEX TB3 DP SLAVE ADDRESS SWITCHES REMOVABLE INPUTS 0 1 IN4 44 41 33 PWR NETWORK 13 IN0 16 IN1 21 5V 24 IN2...

Page 4: ...dress 126 cannot be used in data exchange mode and is reserved for commissioning purpose only You must use the Set Slave Address command to change the internal EEPROM address following power up in ord...

Page 5: ...the length indicated below for your transmission rate For baud rates not shown the lower length of the closest range end points apply i e 100M at 3Mbps Bus Segment Length Limit Per Baud Rate For Type...

Page 6: ...AND END OF A NETWORK OR NETWORK SEGMENT SEGMENT 1 UP TO 1200 METERS UP TO 32 NODES PER SEGMENT END OF SEGMENT TERMINATION ON PROFIBUS MASTER A HOST PC WITH PROFIBUS CARD INSTALLED AND RUNNING APPLICAT...

Page 7: ...IN1 TB1 DIFFERENTIAL CURRENTMONITORING INP Temperature Pressure Level Flow Speed 961PB DCS PLC NOTE 961PB INPUTS ARE NOT ISOLATED CHANNEL TO CHANNEL EXCEPT FOR COMMON MODE VOLTAGES LESS THAN 5V AS SUC...

Page 8: ...oes not include an earth ground screw it may be necessary to strip the cable insulation near the field device and clamp the cable shield to a local grounding bar or surface as shown Connect Earth Grou...

Page 9: ...nd Held ProfiBus Network Maintenance Tools Manufacturer Part Number Special Features Siemens BT 200 Primarily a Cable Tester Comsoft NetTest II Set 4000 7 06C J Includes DP Mono Master Functionality I...

Page 10: ...ort this command and can read the diagnostic information from the Profibus device SYMPTOM POSSIBLE CAUSE POSSIBLE FIX Yellow BUS LED does not light Initialization Problem LED ON if module in data exch...

Page 11: ...one for normal operation and another for accomplishing calibration The normal data exchange definition supports 6 input words 12 input bytes representing your measured values A second calibration def...

Page 12: ...3 6 for the other channels of the same range 8 With user parameter bytes 0 1 select the next range to be calibrated Note 961PB The 4 20mA range is calibrated when the 0 20mA range is calibrated and i...

Page 13: ...model number Range Variability The first 3 channels must share the same range but this can be different than the range of the last 3 channels Optional AC Current Input 961PB Only An optional AC curre...

Page 14: ...4 9 current sink resistors across the inputs Voltage input models use 10 1 precision resistor voltage dividers at the input A multiplexer is used to connect each input voltage to an A D converter sepa...

Page 15: ...figurable for 0 to 20mA 4 20mA 0 11 17mA and 0 1mA DC nominal input ranges A precision 24 9 current sink resistor converts the input current to a voltage that is processed by the A D converter An opti...

Page 16: ...s except 0 1mA This includes the effects of repeatability terminal point conformity and linearization but does not include sensor error Measurement Temperature Drift Better than 50ppm C 0 005 C Analog...

Page 17: ...0 01 of output span per volt peak to peak of power supply ripple Isolation Input channels as a group power and network circuits are isolated from each other for common mode voltages up to 250VAC or 3...

Page 18: ...ty for Class I Division 2 WARNING EXPLOSION HAZARD Do not disconnect equipment unless power has been switched off or the area is known to be non hazardous Interface Standard 3 wire RS 485 multi drop h...

Page 19: ...the Set Slave Address command before completing initialization and assuming the data exchange mode IMPORTANT Address Setting The internal EEPROM address setting and external switch setting is 126 from...

Page 20: ...ive low inputs a value of 1 means the input is ON active low near 0V while a value of 0 specifies the input is OFF or in its high state usually 0V This model includes three user parameterization bytes...

Page 21: ...ory The following table shows the revision history for this document Release Date Version EGR DOC Description of Revision 03 APR 03 A BC KLK Initial release 28 OCT 03 B BC KLK UL updates per ECN 03J02...

Reviews: