38
2) Open the AIM-M300 series IMD fault locating function. Enter the the communication settings menu
and set the LOCAT item to YES, then quit and save to start this function.
3) Address settings. To ensure the realization of fault location function, it is necessary to set
the can communication address of AIM-M300 series IMD, and set the can communication address of
AIL150/AIL160 through this operation. Before setting, make sure that the CAN bus wiring of
AIM-M300(or AIM-M300/SG), AIL150/AIL160 and other products in the same it system is correct, and
a 120 Ω matching resistance is added at the end (the resistance must be added, otherwise
communication may not be possible). You can also connect the AIL150/AIL160 to the head or end of
the CAN bus, and turn all its dial switches to the "1" position). Power on the system, enter the
communication setting menu of AIM-M300(or AIM-M300/SG), set the can communication address, press
enter to confirm, press self check to return and save. If the communication indicators of
AIL150/AIL160 flash during the saving process, the can communication address of AIL150/AIL160 is
also set successfully. The number of addresses is recommended to start at 1.