Terminal Guards
The
fl
ue outlet should be protected with a terminal guard conforming to BS5440-1
if persons could come into contact with it, or if it could be damaged or if it is in a
vulnerable posi
�
on such as where the
fl
ue discharge is within easy reach from the
ground (less than 2m) balcony, veranda or an opening window.
The
fl
ue outlet can be either taken from the standard top exit or converted rear exit of
the appliance.
Terminal Loca
�
ons
Dimension Terminal Posi
�
on
Distance
(mm)
A*
Directly below an opening, air brick, opening window etc.
600
B
Above an opening, air brick, opening window etc.
300
C
Adjacent to an opening, air brick, opening window etc.
400
D
Below gutters, soil pipes or drain pipes
300
E
Below eaves
300
F
Below balconies of car port roof
600
G
From a ver
�
cal drain pipe or soil pipe
300
H
From an internal or external corner
600
I
Above ground roof or balcony level
300
J
From a surface facing the terminal
600
K
From a terminal facing the terminal
600
L
From an opening in the car port (e.g. door , window into the dwelling)
1200
M
Ver
�
cally from a terminal on the same wall
1500
N
Horizontally from a terminal on the same wall
300
P
From a ver
�
cal structure on the roof
600
Q
Above intersec
�
on with roof
150
* In addi
�
on, the terminal should not be nearer than 300mm to an opening in the building fabric
formed for the purpose of accommoda
�
ng a built-in element such as a window frame.