5
Installation
Power supply
SPIDER must be connected to a supply voltage according to the specifications below.
Voltage supply
230 VAC +10% / -20%
Frequency
50/60Hz
Input current consumption
0,004 -> 0,06A
Startup current
<10A
Own consumption
Max. 10W
Fuse
≤250mAT
SPIDER is equipped with a built-in Power bank and can send voltage
failure alarms when the primary power supply disappears.
The SPIDER Power bank (the two green high capacity capacitors) is
located on the bottom of the top print.
WARNING!
Do not disassemble device until Power bank is turned off.
Physical measurements
For the installation of the SPIDER controller, the following specifications may be required.
SPIDER can be mounted on a standard 35mm DIN-rail.
Dimensions
L = 87mm x H = 90mm x W = 62mm
Weight
250g
Cable connection
0.5
–
2,5 mm2
Vibrations (sinus shaped)
10-500Hz, 1G
Installation environments
SPIDER must not be installed in direct sunlight
Humidity
10% - 95% non-condensing
Operation temperature
-20°C to +50°C
Storage temperature
-20°C to +60°C
Maximum operation elevation
Max. 2000m above sea level
Free fall drop
30cm
Enclosure class
IP20
Start-up time total
20-120 sec. (depending on the GSM network)
Build-in power supply
SPIDER has an internal power supply designed for supplying sensors and input and output signals. Power
supply V:
Output voltage
24 V DC
Output current
Max. 100mA
Tolerance
+ / - 20%