30
Pump word: P1=Register 70 P2=Register 72
Warning
Alarm
Bit 6: Pump warning - long operation time (Time > total time / (total starts x 1,5))
Long operation time
Bit 7: Internal
Bit 8: Internal
Bit 9: Pump error - High level switch
Error + High level switch
Bit 10: Pump error - High level
Error + High level
Bit 11: Pump - startet by high level switch
Operation by switch
Bit 12: Pump - Back stopped
Back-stop controlled
Error ModBus
Bit 13: Pump error - repeatedly (needs to be reset)
Suspended
Bit 14: Pump - Manual mode
Locally operated
Bit 15: Pump - Forced to stop by either panel or SRO
Forced to stop
Bit 16: Pump - Manual mode by SRO
Manually
Bit 17: Pump - startet manually by SRO (Requires bit 16 = 1)
Run manually
Bit 18: Stop - manual mode
Stop Mannually
Time / Date
FP32U
Seconds
80
Minuttes
82
Hour
84
Day
86
Month
88
Year
90
System information
FP32U
Id number
0
GSM-signal
94
Description
0-100% (0 decimals)
SPIDER status: Register 92
Status
Warning
Alarm
Bit 0: Emergency control active
√
Bit 1: Emergence control actice 2 pumps
√
Bit 2: Internal power supply failure
√
Bit 3: P1+P2 in error
√
Bit 4: P1 in error plus high level
√
Bit 5: P2 in error plus high level
√
Bit 6: External power supply failure
√
Bit 7: Transmitter error
√
Bit 8: One pump in operation
√
Bit 9: Both pumps in operation
√
Bit 10: Number of pumps controlled (0=1, 1=2)
√
Bit 11: Control in alarm
√
Bit 12: Warning leakage
√
Bit 13: P1 capacity needs update
√
Bit 14: P2 capacity needs update
√
Bit 15: Co-operation capacity needs update
√
Bit 16: IO-external error DI1-4
√
Bit 17: IO-external error DI5-8
√
Bit 18: Waiting for co-operation
√
Bit 19: Back-stop control all pumps
√