RS485 Terminating Resistor - If the MOD9200 is at the end of a RS485 loop a
terminating resistor should be installed to match the electrical impedance characteristic of
the twisted pair loop and prevent signal echoes from corrupting the data.
b.
Network Setup for Transceiver Configuration
A network connection using a RJ45 Crossover cable is required during the initial setup of
the Transceiver for transporting the Transceiver Configuration File via FTP.
Connect the MOD9200 Transceiver (J2) to a 10/100Base-T Ethernet network or use a
crossover cable to connect directly to the PC.
Apply 24 VAC 60 Hz power to the MOD9200 Transceiver.
c.
Setting A New IP Address
The MOD9200 is shipped from the factory with an IP address of 192.168.0.1 and a
subnet mask of 255.255.255.0 .
Note: To initially connect to the Transceiver, the networked PC must have a static
IP address in the form of 192.168.0.X, where X is > 2 with a subnet mask of
255.255.255.0.
The IP Address can be changed by changing the IP Address in the Transceiver Config
File. Open either an existing config file or a new config file using the ACI Programmer
Software.
Click on Settings > TCP/IP Transport