MOD9000BNT BACnet Receiver Installation & Configuration
AUTOMATION COMPONENTS, INC Version : 1.0
2305 Pleasant View Road I0000674
Middleton, Wisconsin 53562
Page 35 of 37
www.workaci.com
(888) 967-5224
6.
24 VAC Input - Connect 24VAC 60 Hz and earth ground to the input
terminals using 20 AWG wire as shown in the product data sheet.
7.
Power up the MOD9200 Transceiver with the BACnet MSTP network.
8.
Use BACnet Device Scan function to identify the MOD9200 Device Instance
& MSTP address.
9.
Verify there is no address conflict with other node in the subnet.
10.
Proceed to read object AI01 to AIXX & AI101 to AI1XX alarm property
(where XX is the last data register configured using the Trs Programmer
Configuration software [For AIXX, XX = Trs MOD9200 data Register
1]).