MOD9000BNT BACnet Receiver Installation & Configuration
AUTOMATION COMPONENTS, INC Version : 1.0
2305 Pleasant View Road I0000674
Middleton, Wisconsin 53562
Page 20 of 37
www.workaci.com
(888) 967-5224
Assign the appropriate digital or relay output “TRANS CHAN” to the data
register by clicking in the cell to open a drop down menu. Click on the
appropriate transmission channel (01 to 04) to select.
The active transmission channels or output number are factory set as follows:
Device
Digital
Analog
RD2402
1 to 2 for relay #1
and relay #2
NA
Wireless relay
output module
RD2432
1 to 4 for relay #1
to relay #4
1 to 4 for analog
output 1 to 4
Wireless digital &
analog output module
h.
Setting the Mesh Network ID for the repeater/router devices
The mesh network ID of the MOD9200 Gateway can be set to specific
network # from 1 to 64. The MOD9200 functions as a network coordinator.
Any repeater/router that has the same network ID will be able to communicate
and channel sensor information to the MOD9200