B5C Operation And Maintenance Manual
85950-301-000 RA
Aug. 05, 2016
20
3.10 Menu “7_RELAY STYLE”
Enabled:
Each relay may be individually set to be enabled or disabled. If it’s
disabled, the relay will always de-actuate no matter what the current gas
concentration.
Default is Enabled.
Normally
De-
energized:
Each relay may be individually set to be normally energized or normally
de-energized.
Default is normally de-energized.
Latching:
Each relay may be set to latch in actuate status until acknowledged by a
front-panel action.
Default is Non-Latching.
ON Delay:
“Delay on Actuation” or “Delay on Make”. For each relay a separate time
delay may be set from 0 to 990 seconds before an alarm condition will
cause the relay to actuate.
Default is 5 seconds.
OFF Delay:
“Delay on De-Actuation” or “Delay on Break”. For each relay a separate
time delay may be set from 0 to 990 seconds before a return to a non-
alarming signal condition will cause the relay to de-actuate.
Default is 5 seconds.
Style:
Normal Relay Style: Work as normal relay.
Buzzer Style Relay: When the relay is used to control a buzzer or horn.
Working as a buzzer style will make the relay have the same function as
the buzzer. It will be switched off when performing the Hush
Buzzer/Relay function in the Tool Menu.
Default is OFF.