B5C Operation And Maintenance Manual
85950-301-000 RA
Aug. 05, 2016
2
Factory Calibration and Default Settings
This B5C CO transmitter has been calibrated in our facilities according to the
manufacturer’s procedures.
SPAN:
B5C-CO-250P:
0 – 250 ppm CO
B5C-CO-1000P:
0 – 1000 ppm CO
CAL GAS:
100 ppm CO balanced with air
The B5C CO transmitter default settings:
Password:
4321
Address:
126
Protocol:
BACnet /MSTP Master at 38.4kbps baud rate
BACnet UTC Offset:
300
Daylight Saving:
Yes
Device Object ID:
4005
LCD Backlight:
Auto
Alarm Settings:
Alarm#
Input
On
Concentration
Off
Concentration
Output Trigger
Alarm1
Instant
25ppm
20ppm
Relay1
Alarm2
Instant
50ppm
40ppm
Relay1, Relay2
Alarm3
Instant
100ppm
95ppm
Relay1,2,3, Buzzer1
Alarm4
Fault
25ppm
23ppm
Relay3, Buzzer3
Alarm5/6/7/8
Disabled
Relay & Buzzer Settings:
Relay#
Normally
Energized Latch On Delay Off Delay
Style
Relay1
NO
NO
5 seconds 5 seconds
Normal Relay
Relay2
NO
NO
5 seconds 5 seconds
Normal Relay
Relay3
NO
NO
5 seconds 5 seconds
Normal Relay
Buzzer1/2/3
Disabled
*Note: Each setting can be modified in B5C Menu
*Note: For BACnet settings, see 85950-103-000 Rx (B5 PIC Statement)
*Note: Per UL standard 2075, this B5C sensitivity limits are superior to the standard
sensitivity requirements defined in UL2075.