Page 16
IAQ-
INDOOR AIR QUALITY
Tek
MONITOR & SENSOR
41 EA GLE R OAD
DANB URY, CT 06810
PHONE ( 203) 791- 1400
Specifications
System Accuracy
Intake Velocity
750 to 200 FPM; ± 5 % reading
200 to 100 FPM; ± 10% reading
Probe and Transducer
1/4" BARB
FITTINGS
6 7/8"
1/4-20UNC
INSERTS
3 1/2"
M
ANUF
ACT
URED B Y
DIA 8 1/2"
DIA. 3/16"
4 1/8"
hi g
l ow h
4"
7 1/2"
7 1/2"
Temperature
Operating: -40 to 120 ±°F
Storage: -40 to 150 °F
Air Velocity Capabilities
Discharge of intake louver- 75 to 750 FPM
Free Air, before damper- 100 to 1000 FPM
Probe
Material: PVC/ABS
Fire Rating: UL-94-V0 and UL-94-5VB
Quantity Required:
Louver area <64 square feet:
1 per 12 sq. ft. with aspect ratio of 1 to 1.5.
1 per 8 sq. ft. with aspect ratio greater than 1.5
Louver area > 64 square feet:
1 per 16 square feet
Weight: 1.5 lbs.
Tubing Connections: 1/4" barb fittings
Transducer
Enclosure: NEMA-4X Watertight
Electrical Connection: Integral Cable
Weight: 1.5 lbs.