background image

page 10

Fig. 3

1.11  EXPLODED VIEW - WR version for ceiling installation

page 27

decrease the pressure and clockwise to increase
the pressure (this operation can be carried out
only when using methane gas G20).

Turn the room thermostat dial to the minimum
value and check that the burner shuts off.

Remove the pressure gauge tube and tighten
the pressure regulator screw, carefully checking
the seal. Replace the regulator protection plug.

WARNING! When the burner turns off, the fan
will continue to operate for a few minutes, to
properly cool the exchanger. Therefore, it is
important not to turn off the air heater using
the mains switch, that also cuts off the power
supply to the fan, since this might lead to
overheating.

Then repeat the start-up operation to observe
and check that the burner has ignited correctly
and that the flame is stable.

For installation with ducts (WD). While the
burner is functioning, use the switch (F) to select
the minimum fan speed, and run the unit for
approximately 20 minutes. During this period
verify that the heated air freely and properly exits
the duct’s grilles or outlets. If there are any
obstacles or incorrect adjustments to the outlets,
or if the size of the ducts is incorrect, the safety
system could be activated. If this occurs, try to
locate and eliminate the possible causes of the
overheating.

Once the checks have been completed, put the
casing’s panels back in place and make sure
that they are correctly attached. Place the plastic
finishing caps in any fastening holes that have
remained open.

5.3 USER INFORMATION

It is recommended that the user be informed
about all the procedures necessary to use
the air heater correctly, with particular
reference to the ignition and shutdown
phases and about the importance of periodic
tests, which must be performed at least once
every year by skilled personnel.

6.  GAS TYPE CHANGE

6.1 SWITCHING FROM GAS IN THE SECOND

GROUP (NATURAL GAS) TO GAS IN THE
THIRD GROUP (LPG)

a) Check that the envelope supplied with the air

heater contains the replacement injector, the
screw block with pin and the adhesive label,
on which to indicate the new type of gas being
used, to replace the original one

b) check that the diameter of the injector

indicated for the type of gas to be used (see
technical data table on page 7)
 corresponds
to what is stamped on the injector.

c) Close the gas on-off valve and disconnect the

electric power supply. Remove the air heater
casing’s right angular panel by first removing
the two screws located on the front (protected
by plastic caps) and then using the point of a
screwdriver as a lever to release the fastening
springs in the rear.

d) Remove the 2 screws which attach the gas

supply pipe connector to the combustion
chamber  (fig. 24). Gently remove the
connector until the injector is free and unscrew
it using a 10-mm hex wrench. Insert a new
injector and retighten it to ensure a proper
seal. Put the connector back in place and
attach it to the combustion chamber with the
two screws.

e) Unscrew the pressure regulator protection

plug located on the gas unit. Insert the screw
block with pin in the place of the protection
plug and tighten it so as to put the regulator
out of service (fig. 24)Keep the pressure
regulator protection plug for future use.

f) insert the water column pressure gauge tube

into the upstream pressure inlet on the burner
(fig. 23) after having backed off the closing
screw a few turns

g) start the air heater according to what is

indicated in point 5.2. Check that the supply
pressure corresponds to what is indicated in

Fig. 23

GAS UNIT

Electrical
connection

Pressure
regulator screw

Gas

Pressure test-point

Pressure inlet

Summary of Contents for W

Page 1: ...A2B srl Via d Ancona 37 60027 Osimo An Tel 071 723991 Fax 071 7133153 Web Site www accorroni it E mail a2b a 2 b it Technical information W WR WD Gas fired convection heaters with fan W WR WD...

Page 2: ......

Page 3: ...al data table 7 1 10 Dimensions WR and WD versions 8 page 36 Gas fired convection heaters with fan W WR WD series Models 8 10 Technical Information Code 25259501 GB Rev 3 10 05 05 WARNING Whentheburne...

Page 4: ...open and the electric power supply is on 10 3 2 The instructions to the control panel functions which follow refer to fig 35 a Turn the room thermostat knob E clockwise to the maximum value b Turn swi...

Page 5: ...e user to carry out the operations indicated in point 11 1 of this manual at least once every two months 9 2 YEARLY INSPECTION 9 2 1 Control and safety devices WARNING Specific technical skills are re...

Page 6: ...this solution would present technical or functional advantages For ceiling installation WR version in rooms where there is not enough free space on the walls For ceiling installation with duct con nec...

Page 7: ...d a combustion chamber which houses an atmospheric burner which generates an axial flame The combustion products are exhausted outdoors by a centrifugal fan The ventilation unit which is made up of tw...

Page 8: ...e the remodelingofbuildingunitsasresidences offices stores orworkshopsiscomplicatedbyaseriesof technical and structural problems that make it difficult to install a traditional heating system These sy...

Page 9: ...first checking the on off valves on the delivery line Completely bleed off any residual air and restart the unit b Thegassolenoidvalvesdonotopenbecause the coils are malfunctioning or their electrica...

Page 10: ...tch does not reset the contacts to the proper position see point 8 4 d The flue gas expeller fan s motor has failed and the differential pressure switch will not allow startup to proceed Change the fa...

Page 11: ...y plastic caps and then using the point of a screwdriverasalevertoreleasethefastening springs in the rear d Remove the 2 screws which attach the gas supply pipe connector to the combustion chamber fig...

Page 12: ...ses and about the importance of periodic tests which must be performed at least once every year by skilled personnel 6 GAS TYPE CHANGE 6 1 SWITCHING FROM GAS IN THE SECOND GROUP NATURAL GAS TO GAS IN...

Page 13: ...ressure of 20 mbar Instead if gas from the third group is used LPG first carry out the operations described in point 6 1 5 1 4 Check that the gas on off valves on the meter and on the air heater are o...

Page 14: ...the wall with a center distance of 120 mm Insert the screw anchors and attach the rear part of the panel to the wall Put the front part of the panel back by snapping it in place Ifyoushouldneedtoinse...

Page 15: ...R and WD WARNING For your safety due to the weight of the unit and the possible difficulties of installingit itisadvisabletouseamechanical hoisting device for positioning the air heater For these same...

Page 16: ...ts must be made on the free ends opposite the wind protection terminals Make sure that they are cut squarely and trim off any burrs NOTE The exhaust flue is the longer of the two c Insert the ducts in...

Page 17: ...R and WD Once the unit s position has been determined bend the supplied paper template on the dashed line and apply it to the ceiling with adhesive tape fig 17 a Indicate the position of the four hole...

Page 18: ...from ACCORRONI S r l In any case any increases to the length of the ducts must respect the limits specified in the next point 4 2 2 Duct length limits If the duct passes directly through an outside w...

Page 19: ...between the rear part of the unit and the wall so as to permit correct air intake and to allow the filter to easily be removed for cleaning fig 13 For the WD version make sure that the air intake sys...

Page 20: ...k making sure to observe the instructions reported on the box indicated by the special graphic symbols When delivered check that no visible damage on the packing and or on the appliance has occurred d...

Reviews: